Rugged instrumentation for reliable measurement and control

Applications By Industry

Temperature stratification is normal in distillation columns. However, in some chemical or refinery processes too much temperature differential between layers within the column can yield poor quality product or create a dangerous condition that could lead to a column rupture or explosion.

The SLA can help mitigate this situation by accepting up to six temperature inputs, in this case thermocouples, and performing an absolute differential calculation between any temperature sections to ensure that temperature stratification levels within critical zones in each column never differ by too much. The SLA can implement up to 16 alarms based on any input, equation, or combination of inputs/equations. This Figure shows the SLA installed in a temperature alarm Safety Instrumented System (SIS) application.

 High Temp SIF

Download the PDF file

In this application, three separate alarms, one for each zone, are configured to alarm if more than a 50degC temperature differential exists between the zone’s lower and upper temperature points. The temperature differential for each zone is calculated with an absolute differential equation via SLA’s advanced configuration settings. An alarm voting architecture is put in place where relay outputs will be activated to trigger an alert (1oo3 voting), warning (2oo3 voting), or shutdown (3oo3 voting) situation. A contact closure wired to one of the SLA’s four available Discrete I/O channels is used to release latching alarms and/or relays.

The BPCS (Basic Process Control System) monitors each zone’s temperature differential via the SLA’s three analog outputs. All inputs, outputs, alarms, faults, and various other parameters from the SLA are transmitted via MODBUS/TCP over Ethernet to the BPCS.

The SLA’s built-in web server also provides quick and easy read-only viewing of inputs, alarms, outputs, internal variables, faults, warnings, and more via any standard web browser. Prebuilt web pages include simple to navigate menus and tables that neatly lay out all of the SLA’s parameters.

 

Key attributes:

  • SIL 2/3 capable exida® approved to IEC 61508:2010 standard
  • Easy to use equation editor allows for quick absolute value temperature calculations
  • Voting architecture alarms of 1oo3, 2oo3 and 3oo3 simple to configure with checkboxes
  • -40 to 85 degrees Celsius ambient temperature operating range
  • Standard MODBUS/TCP protocol sends all process and diagnostic data to BPCS

If you’d like to talk to sales or request a quote, call us at 1 (800) 999-2900 in the US and Canada or +1 (818) 894-7111 and select 1 for Sales, or send us an email via our online form.

 

New call-to-action

Upstream gas wellheads can experience extremely high pressure and surges. To protect personnel and equipment, wellhead casing pressure is often monitored in case there is a situation where the wellhead needs to be shut down. Traditionally simple pressure switches were used, but today companies are required to implement proper safety systems. In addition, upstream gas wellheads often reside in remote locations where access to electricity and harsh conditions propose significant challenges. Moore Industries SLA Safety Logic Solver and Alarm offers an effective and reliable solution for these applications due to its unique set of characteristics, which include exida® IEC61508 approvals, built-in voting logic, rugged housing, ability to run off 10.5-30Vdc power, and built to withstand ambient temperatures that have an operation range from -40 to 85 degrees Celsius.

 Remote Solar Power HIPPS

Download the PDF file

In the above gas wellhead application, three separate smart HART pressure transmitters are wired to the SLA (HART data from the pressure transmitters can also be passed thru to the SLA’s three optional analog outputs when required). With its built-in voting logic capability, the SLA performs a 2oo3 safety voting architecture to shut down the well when dangerous conditions exist. The SLA’s built in loop power supply on each of its three channels provides operating power to all three pressure transmitters. The SLA has up to four digital I/O channels that can be configured as inputs or outputs. In this application,n one of the digital inputs is configured to reset the latching ESD Valve relay output but could be utilized to reset any of the SLA’s 16 internal alarms or other SLA relay outputs. Finally, due to the remote nature of this application, the SLA is powered by 10.5-30Vdc generated through a remote solar power system.

Key attributes:

  • SIL 2/3 capable exida® approved to IEC 61508:2010 standard
  • Requires only one instrument for voting applications with built-in voting logic capability
  • Meets 10.5-30Vdc power requirement for solar or battery backup systems
  • -40 to 85 degrees Celsius ambient temperature operating range
  • Rugged aluminum casing which helps dissipate heat and provides protection against radio frequency and electromagnetic noise in harsh environments.

If you’d like to talk to sales or request a quote, call us at 1 (800) 999-2900 in the US and Canada or +1 (818) 894-7111 and select 1 for Sales, or send us an email via our online form.

New call-to-action

Upstream gas wellheads can experience extremely high pressure and surges.  In order to protect personnel and equipment wellhead casing pressure is often monitored in case there is a situation where the wellhead needs to be shutdown.  Traditionally simple pressure switches were used but today companies are required to implement proper safety systems. Figure 13.1 shows the SLA installed in a remote oil and gas wellhead application using 2oo3 voting logic to ensure pressure protection.

 HIPPS 2oo3 Voting System

Download the PDF file

In this application, to protect personnel and the process from high pressure spikes, the three separate pressure transmitters are wired to the SLA where it can perform a 2oo3 safety voting architecture to shut down the well when dangerous conditions exist. The SLA’s built in loop power supply on each of its three channels provides operating power to all three smart HART pressure transmitters. The HART signal from the three pressure transmitters is passed-through to each of the SLA’s corresponding analog outputs so the RTU/PLC has direct access to all HART programming, variables, and diagnostics of each connected transmitter.

The retransmission of these three pressure transmitters by the SLA, versus wiring in series with the RTU/PLC input cards, provides higher availability to the safety function since a catastrophic failure in the analog input cards or the RTU/PLC itself doesn’t affect the 2oo3 logic shutdown function of the SLA.

Additional relay outputs of the SLA also keep the RTU/PLC informed of shutdown status and any input faults experienced by the SLA. A digital contact input allows any alarm or relay configured as latching to be manually reset. Finally, all inputs, outputs, internal equations, variables, alarms, relay status and more are digitally transmitted to the RTU/PLC via a read-only MODBUS RTU signal. 

Key attributes:

  • Simple to configure 2oo3 voting alarm with check boxes and pull-down menus
  • SIL 2/3 capable exida® approved to IEC 61508:2010 standard
  • HART pass-through of pressure transmitter diagnostics to RTU/PLC
  • SLA provides 24Vdc power to all three pressure transmitters for ease of wiring
  • -40 to 85 degrees Celsius ambient temperature operating range
  • Standard MODBUS RTU protocol sends all process and diagnostic data to RTU/PLC

If you’d like to talk to sales or request a quote, call us at 1 (800) 999-2900 in the US and Canada or +1 (818) 894-7111 and select 1 for Sales, or send us an email via our online form.

New call-to-action

Plants that have large fluctuations in flow demand, like potable water plants, often need large flow capacity measuring devices that don’t create large pressure reductions. Venturi tubes are good for these applications, but often if the flow span is large, consistent accuracy across the entire flow range is difficult to achieve. One way to alleviate this is to use double stacked differential pressure transmitters where one DP transmitter is ranged for lower flow rates while the other handles higher flow rates. With this type of configuration, there needs to be some type of smart device involved to automatically switch between transmitters to achieve the best flow accuracy results.

The SLA Safety Logic Alarm provides this decision-making capability and the safety layer of protection needed to alert the plant when demand has reached very high levels. While safety PLCs can accomplish such tasks, there may be a number of reasons why it is not convenient: cost, remote locations, difficulty of programming, or simply that the PLC has no spare memory capacity. This figure shows the SLA installed as a high-resolution flow calculator and safety alarm.

 Hi Res Flow Calc Alarm

Download the PDF file

This application includes two differential pressure transmitters connected to the pressure ports of a venturi tube, ranged 0-13 million gallons/day and 0-40 million gallons/day for low and high flow rates respectively. Each of the smart HART differential pressure transmitters is powered by the SLA and their HART signals are passed through to PLC input cards. The SLA primarily serves as a safety logic alarm to notify the PLC when extremely high-demand situations occur.

Additionally, the PLC and SCADA system need to monitor accurate flow rates from the venturi tube. To ensure that the 4-20mA flow signal, and the MODBUS registers also representing the flow rate are as accurate as possible, the SLA is programmed to switch between the differential pressure transmitters, depending on current flow rates. The flow rates are calculated with a differential pressure flow equation via SLA’s advanced configuration settings. When flow reaches a rate of 12.9MGD, the SLA automatically switches to the higher-ranged DP transmitter and automatically switches back to the lower-ranged DP transmitter when flow falls below 12.9MGD. This assures maximum flow rate accuracy across the entire flow rate span.

The SLA also retransmits each of the DP transmitter signals back to the PLC and provides relay outputs when the flow rate exceeds 39MGD, the high-range DP transmitter is selected, or when there are system or input faults captured by the SLA. A digital contact input allows any latched alarms or relays to be cleared. The SCADA system and PLC receive all inputs, outputs, internal equations, variables, alarms, relay status and more via the MODBUS/TCP read-only signal.

Key attributes:

  • SIL 2/3 capable exida® approved to IEC 61508:2010 standard
  • -40 to 85 degrees Celsisus ambient temperature operating range
  • Simple to configure logic for flow range selection for high-resolution flow calculation
  • HART pass-through of pressure transmitter diagnostics to PLC & SCADA system
  • Standard MODBUS/TCP protocol sends all process and diagnostic data to PLC

If you’d like to talk to sales or request a quote, call us at 1 (800) 999-2900 in the US and Canada or +1 (818) 894-7111 and select 1 for Sales, or send us an email via our online form.

New call-to-action

Many critical processes require that flow rates are closely monitored for both product quality and safety. Some of these processes are remotely located in a facility from the BPCS (Basic Process Control System). When calculations like mass flow are required for safety considerations, this can sometimes add precious decision-making time to an already burdened BPCS. With the SLA’s built-in equation editor, calculations can be done remotely and oftentimes faster so process shutdowns can help mitigate dangerous situations. Figure 13.3. shows the SLA installed in a high temperature and flow Safety Instrumented System (SIS) application.

 Hi Temp Flow SIF

Download the PDF file

This application requires that a temperature, pressure, and volumetric flow signal be used to calculate mass flow to ensure a safe and proper flow rate to the process. Should mass flow or temperature rise too quickly, a dangerous process condition could occur.

Three loop-powered transmitters are powered and wired into the three isolated SLA input channels. The SLA uses built-in Rate of Change Alarms that monitor mass flow and temperature over time to prevent unwanted surges in process conditions that could lead to a dangerous situation. The SLA uses voting logic (1oo2) to quickly shut down the process in the event of quick increases of mass flow or temperature.

To minimize nuisance trips the alarms are configured as high availability, which means they will not trip if there is an input failure, only when the rate of change event occurs in temperature and/or mass flow. To ensure the integrity of the safety function, input faults along with any system faults are signaled to the BPCS.

The remote BPCS is continually updated with process conditions by receiving three analog outputs from the SLA representing temperature and pressure readings along with the calculated mass flow. The HART signal from the connected temperature and pressure transmitters is passed-through the SLA so any monitoring of HART variables and diagnostics or programming of these connected instruments can be performed. Note that since the flow transmitter is NOT a smart HART transmitter no HART signal is passed through to the third analog output channel.

Status of the shutdown function and any input or SLA faults are also sent to the BPCS via SLA relay output contacts. An input contact is used to manually reset any latching alarms, faults or relays. A system startup delay is set to suppress flow and temperature alarms which would initiate the shutdown logic. All inputs, outputs, alarms, internal variables, and faults along with various other parameters are transmitted via a secure digital and read-only MODBUS/TCP signal over Ethernet.

Key attributes:

  • SIL 2/3 capable exida® approved to IEC 61508:2010 standard
  • -40 to 85 degrees Celsisus ambient temperature operating range
  • Rugged aluminum casing which helps dissipate heat and provides protection against radio frequency and electromagnetic noise in harsh environments
  • Crital HART pressure and temperature transmitter data passed through SLA to BPCS
  • Voting logic and mass flow calculations easily programmed

If you’d like to talk to sales or request a quote, call us at 1 (800) 999-2900 in the US and Canada or +1 (818) 894-7111 and select 1 for Sales, or send us an email via our online form.

New call-to-action

In oil & gas refineries, remote extraction sites and power generating facilities long cable runs can be necessary. However, those long runs can cause significant voltage drops. When a process facility needed to add local displays to their Safety Instrumented System (SIS) loops, voltage consumption was the critical specification that had to be scrutinized.

 Low Voltage SIL 3 Capable Indicator for Level Monitoring

Download the PDF file

After considering multiple loop displays, the Process Engineers learned that the Moore Industries SLD SIL 3 Capable Functional Safety Programmable Loop Display only consumes a maximum of 2.3Vdc, which is much more tolerant of line voltage drops than other loop displays. The SLD is also available with a Loop Maintenance Diode option, which allows the SLD to be removed from the loop for maintenance without interrupting your safety function. Of additional convenience was the SLD’s dual conduit ports that facilitate input and output wiring when adding displays to loops, where most other loop displays only include one conduit connection port and therefore often requires an additional junction box. With the advantage of a lower loop voltage consumption and two cable entries/ports, the SLD decreased the installation cost and increased the voltage available for the safety level transmitter in the loop.

Key attributes:

  • SIL 3 Capable Display
  • Low 2.3Vdc Power Requirement
  • 2-port field mount housing
  • Loop Maintenance Diode Option

Download Datasheet

Why Monitor Power?

Measuring power usage is important Moore IndustriesWhy monitor power usage in your process? With AC power consumption and measurement drawing ever-more attention throughout the process industries, an understanding of basic AC parameters becomes increasingly important. Our free downloadable Power Transducer’s User Guide uses illustrations and simple definitions to explain the basics of AC power and its uses in the process industries. Monitoring your process’s power usage has never been more important, as many businesses are attempting to cut down on unnecessary power use with efforts to go green and contribute to the conservation of our environment. Download our free Power Transducers User’s Guide to see how Moore Industries can help you effectively monitor your power usage so you can ensure you are using only the power you need, saving you money while reducing your environmental impact.

What are some benefits of Monitoring Power Usage?

By continuously monitoring your power usage you will be able to trend and detect which equipment or instruments are consuming considerable amounts of power. This gives you the opportunity to take corrective action when necessary. Continuous power usage monitoring also helps to ensure that you are being charged only for the power you are using.

Plus, improvements you make to ensure machinery is operating effectively and efficiently reduce your demand on the power grid and reduce the overall impact on the environment

Power Transducers User s Guide

How can Moore Industries Help?

Moore Industries created this Power Transducers User’s Guide with illustrations and simple definitions to explain the basics of AC power and its uses in the process industries, which can be downloaded below. After reading this guide you should be able to apply the basic principles needed to use power transducers. In this guide you will find the following information:

 

  • Beginning Definitions for Electricity and AC Power Measurement
  • Basic Concepts of AC Power
  • Common AC Power Systems
  • Monitoring Common AC Power Systems
  • Taking Watt and VAR Measurements
  • Reference Charts, Calculations, and Wiring Diagrams
  • Power Transducers Available from Moore Industries

Download our Power Transducer User’s Guide to learn how you can effectively employ our power transducers to save your plant money, reduce your unnecessary power usage, and limit your overall impact on the environment.

Power Transducer Users Guide

Do you already know about AC Power Monitoring or want to learn more about Moore Industries AC Power Transducers? Check out this blog to learn more.

Instruments designed with Users in Mind

Power usage monitoring made easy Moore IndustriesMonitoring and recording voltage and current requires the use of volt and current transducers. The output signals from these transducers can be used to provide input to meters and activate alarms or other devices should current or voltage fall outside of a safety range.

Moore Industries power transducers feature utility-grade design and construction to provide years of accurate operation. Each model also features a low burden power requirement and a proven ability to maintain stability. For the ultimate quality check, we burn-in and thoroughly test every single unit manufactured. Our rugged and reliable power transducers are the ideal solution for monitoring power usage within your process. Here are some of the main benefits of the Moore Industries Power Transducers:

  • Low burden power requirement
  • Stable function/operation
  • Resilient terminal blocks
  • Easy-to-install
  • Standard wiring and footprint sizes
  • Utility-grade design and construction
  • Rugged metal housing

Discover AC Power Transducers from Moore Industries here.

Contact us at any time regarding your Power transducer needs – we’ll be glad to help! Call Toll-free in US and Canada: +1-800-999-2900 or +1-818-894-7111.

Email us at This email address is being protected from spambots. You need JavaScript enabled to view it. or visit our Contact page and complete the form.

Need to learn the basics about AC Power Transducers? Download our Power Transducers User’s Guide

Temperature sensor failure can wreak havoc on processes where maintaining temperature is critical and monitoring must be continuous. Whether it’s a runaway temperature that spoils a batch or a process interruption when an alarm shuts down the process due to a sensor failure, you lose time and money.

Dual input temperature transmitters with built-in backup and failover protection such as the THZ 3 and TDZ3 Dual Input Smart HART Temperature Transmitters from Moore Industries allow you to designate either of the sensors or inputs as the primary measurement and the secondary input acts as a backup sensor in case of a primary sensor failure.

One real world example involves the monitoring of critical temperatures in a chemical batch processing vessel (see Figure 1). It’s important to have the ability to maintain your temperature measurement in case of sensor failure.  Single input temperature transmitters would require redundant sensors and transmitters that add to installation and maintenance costs.  The THZ3 and TDZ3 with dual sensor input automatically switches to the backup sensor when the transmitter senses a primary sensor failure. This means that process monitoring can safely continue without interruption until the problematic sensor is replaced.

Dual Input Temperature Allow for Uninterrupted Process Monitoring figure1

Figure 1.  When reading critical temperatures in a chemical batch processing vessel, failover protection allows the secondary input of the Dual Input TDZ3 to act as a backup sensor when the primary sensor fails.

Multidrop Networks Save Time and Wiring Costs

The dual input capability also means that you can increase your temperature measurement points in a multi-dropped HART network.  HART versions 5 and 6 allow up to 16 THZ3 or TDZ3 transmitters to be multi-dropped on one digital HART loop to monitor up to 32 temperature points. This reduces your DCS Input count, wiring costs, and transmitter count.

Any combination of THZ3 and TDZ3 transmitters can be connected in parallel onto a HART digital communication link (see Figure 2). This means you can use a single loop, instead of separate loops, to connect multiple transmitters. In a multidrop network, the transmitter’s measured process variable is output digitally, so the 4-20mA signal (locked at 4mA) is not used.

Dual Input Temperature Allow for Uninterrupted Process Monitoring figure2

Figure 2.  Multi-dropping several Smart HART transmitters onto a single digital data link saves time and money. Utilizing THZ3 or TDZ3 transmitters with dual inputs allows for cost-effective monitoring of several temperature points on one HART input channel.

 

A HART-based control system uses each transmitter’s individual address to configure, poll and view the transmitter’s data. A HART Communicator or other HART master with programming capability can be used in this configuration to access information from, or transmit configuration information to, the transmitter from anywhere on the HART loop.

Additional Dual Sensor Input Benefits

  • Average and Differential measurements can be utilized to average the two input measurements or select either the differential (A-B or B-A) or absolute difference between the two inputs.
  • High-Select and Low-Select features which enable the transmitter to continuously monitor two separate inputs and designate either the highest or lowest input as the source for the analog output or PV.
  • Dynamic Variable Mapping that permits the user to assign either the input or the calculated result of the inputs to any of the four HART variables (PV, SV, TV and QV) that can be read by any HART-compatible host system.

Device Intelligence for Smarter Monitoring and Control

The THZ3 and TDZ3 come with Device Intelligence, a series of features for smarter control and monitoring including:

  • Sensor drift and corrosion detection that checks and alerts users when the sensor is drifting out of a preset range or when the resistance due to corrosion exceeds set parameters.
  • Smart range alarms with four HART alarms – set to any input or calculated input – that detect when the variable is within or outside of user preset limits.
  • A High Availability option that enables the selection of how the AO behaves when there is an input failure or out-of-range value detected by the transmitter. This prevents nuisance alarms on startups or batch process shutdowns.
  • Input simulation capability allowing manual input of a direct or calculated value. This essentially simulates a real input, allowing users to test the AO or any HART diagnostic and range alarms.

Dependability and Accuracy

Users can rely on the accuracy and dependability of the THZ3 and TDZ3. Their input-to-output analog accuracy of up to ±0.014°C (±0.025°F) utilizing sensor matching and trimming over a 100°F span is the absolute best in the industry.  The transmitters feature 20-bit input resolution and deliver exceptional input accuracy for all sensor types. 

Plus, Moore Industries’ patented continuous sensor diagnostics feature can save you from costly lost production and hours of troubleshooting. Advanced RFI/EMI protection and ambient temperature compensation guard against environmental factors that can quickly degrade measurement accuracy, while long-term stability provides up to five years between scheduled calibrations.

SIL 3 Capable STZ for Safety-Related Applications

End users who need a dependable and accurate temperature transmitter for use in Safety Instrumented Systems (SIS) where dangerous processes occur can turn to the SIL 3-capable STZ Functional Safety Dual Input Smart HART Temperature Transmitters. Part of the FS FUNCTIONAL SAFETY SERIES, the STZ has been certified by exida after rigorous evaluation to ensure conformance with strict IEC 61508:2010 standards for safety-related applications.

As with the THZ3 and TDZ3, the STZ has a dual sensor input that provides Backup and Failover Protection to reduce process interruptions. For example, the temperature is often a critical measurement in reactors, especially processes with the potential for thermal runaways due to exothermic reactions. Utilizing the failover/backup feature with dual sensor input on the STZ can help a Safety Instrumented System (SIS) mitigate potentially dangerous situations (See Figure 3).

Dual Input Temperature Allow for Uninterrupted Process Monitoring3

Figure 3.  Temperature is often a critical measurement in reactors, especially processes with the potential for thermal runaways due to exothermic reactions. Utilizing the failover/backup feature with dual sensor input on the STZ can help Safety Instrumented Systems (SIS) mitigate potentially dangerous situations.

 

Discover Dual Input Temperature solutions from Moore Industries at www.miinet.com/HART-Temperature

Moore Industries’ article The Ins and Outs of I/O has been published by Control Engineering Europe in the June 2022 issue (p. 22).  The article outlines the various types of I/O, pointing out that although defining the difference between Local I/O and Remote I/O is straightforward, distinguishing Distributed I/O is more nuanced and complicated. More complex Distributed I/O harnesses all the capabilities of Remote I/O and more because it involves equipment that can be distributed throughout a process plant or automation facility.  This equipment contains its own advanced CPU and real time operation system that allows localized control and monitoring, without the concern of continuous communication with its host Controller/CPU. Read the article to get the whole story.

View article

Moore Industries’ article Sensor Integrity Ensures Temperature Measurement Accuracy has been published by InTech Focus in the May 2022 Temperature & Pressure eBook issue (p. 19).  The article points out that whether you are measuring or controlling temperature, measurement accuracy begins with the sensor – better sensors make better process measurements. The article goes on to address the multiple factors that affect the accuracy and provides effective techniques and selection tips. Read the article to get the whole story.

View article

WORM and Solid Sheath Sensors data sheetWe’ve been busy revamping our temperature assemblies and sensors product offering to make it far easier for you to find what you need and tell us what you want. Many items that were custom-order are now selectable by a part number, with the necessary variables easy to factor in. To make it easy to find the part you need, our four “RTI” Ready-to-Install assemblies data sheets have been consolidated into one titled Temperature Assemblies – WORM and Solid Sheath Sensors.

This new data sheet is designed to acquaint you with the spectrum of our sensors, thermowells and accessories to help you select and configure the components you need for your unique application. Information in this data sheet includes:

WORM Flexible Temperature Assemblies

  • WORM Sensor Specifications
  • Ready-to-install Thermowell Temperature Assemblies
  • Worm Surface Mount Assemblies
  • WORM Upstream Flex-Armor Assembly
  • WORM Replacement Kits
  • Build Your Own WORM
  • Thermowells Only
  • Replacement Sensors and Components

Solid Sheath Temperature Assemblies

  • Full Thermowell Assembly
  • Fixed Immersion Assemblies
  • Sensor Assemblies Using Existing Thermowells
  • Flex Armor or Stainless Steel Braid Sensors
  • Replacement Sensors and Spare Parts

Temp Assy Sens catalog thumbnail 060922All of the model and part numbers you need for your temperature assembly are provided in this new data sheet. You can download the data sheet from our Download Center or use this link.

We have also updated our online catalog Temperature Assemblies and Sensors section with new temperature assembly groupings, and access to the data sheet right on each product group page allowing you to easily start your request for a quote. See the products available in the online catalog Temperature Assemblies and Sensors section  

Contact us at any time regarding your particular temperature assembly configuration – we’ll be glad to help! Call Toll-free in US and Canada: +1-800-999-2900 or +1-818-894-7111.

Email us at This email address is being protected from spambots. You need JavaScript enabled to view it. or visit our Contact page and complete the form.

 

The ambient air or environment plays a critical role in many manufacturing industries that require maintaining sterile or aseptic environments served by HVAC systems. Controlling different parameters, such as the air’s temperature and humidity is certainly vital for ideal manufacturing conditions. But if continuous flow rates are not also tightly monitored and controlled, humidification and temperature controlling equipment cannot perform as originally designed.

HVAC Airflow Sensor Monitoring

Download the PDF file

To verify that proper flow rates are supplied to the lab’s pneumatic valves, an ECA Current Alarm Trip is used to alarm on low airflow conditions. The ECA comes standard with two SPDT alarm outputs and a TX option (24VDC @ 25mA) that powers the loop powered Airflow Sensor so no additional wiring to a separate 24DC auxiliary power supply is needed. Setpoints for the two alarms are set with front panel potentiometers adjustable from 0-110% of input span. This is very useful for NAMUR compliant type Airflow Sensors as one of the two alarms can be set at >21mA, indicating a failed transmitter condition per NAMUR standards. Field configurable via selectable jumpers, each alarm function can be site configured for high/low and Failsafe/Non-Failsafe relay action. This fast acting 50msec response time alarm, also comes standard with an adjustable deadband capability of 1-20%. 

Key attributes:

  • Powers and Receives 4-20mA Signal from Airflow Sensor
  • Dual field configurable alarms capable of alarming on NAMUR failure output range from Airflow Sensor
  • Relays rated 5A, 250VAC
  • 50msec response time
  • Adjustable deadband for each alarm

 

Download Datasheet

In municipal and industrial wastewater treatment, aeration is part of the secondary treatment process. The activated sludge process is the most common option in secondary treatment. In industrial use, a common method of aeration is air diffusion method, in which air is diffused into a receiving vessel containing counter-current flowing water, to remove dissolved gases, such as carbon dioxide, Hydrogen Sulfide or methane, and to oxidize dissolved metals such as iron. If air header flow rates being supplied by compressors are not sufficient, the secondary treatment process will be incomplete and may yield contaminated water to rivers and other environmental water sources.

Water treatment Airflow Sensor Monitoring
 Download the PDF file

To verify that proper flow rates are supplied to the lab’s pneumatic valves, an ECA Current Alarm Trip is used to alarm on low airflow conditions. The ECA comes standard with two SPDT alarm outputs and a TX option (24VDC @ 25mA) that powers the loop powered Airflow Sensor so no additional wiring to a separate 24DC auxiliary power supply is needed. Setpoints for the two alarms are set with front panel potentiometers adjustable from 0-110% of input span. This is very useful for NAMUR compliant type Airflow Sensors as one of the two alarms can be set at >21mA, indicating a failed transmitter condition per NAMUR standards. Field configurable via selectable jumpers, each alarm function can be site configured for high/low and Failsafe/Non-Failsafe relay action. This fast acting 50msec response time alarm, also comes standard with an adjustable deadband capability of 1-20%. 

Key Attributes:

  • Powers and Receives 4-20mA Signal from Airflow Sensor
  • Dual field configurable alarms capable of alarming on
    NAMUR failure output range from Airflow Sensor
  • Relays rated 5A, 250VAC
  • 50msec response time
  • Adjustable deadband for each alarm

 

Download Datasheet

Many industrial facilities have R&D divisions or labs onsite to assist with small batch runs or testing to ensure that large scale production has met or will meet quality control standards. Often these labs are filled with smaller pneumatic valves that use air from onsite industrial compressors. If air header flow rates being supplied by these compressors are not sufficient, expensive test batches can be ruined or critical lab results can fail.

 Small Batch Airflow Sensor Monitoring

 Download the PDF file

To verify that proper flow rates are supplied to the lab’s pneumatic valves, an ECA Current Alarm Trip is used to alarm on low airflow conditions. The ECA comes standard with two SPDT alarm outputs and a TX option (24VDC @ 25mA) that powers the loop powered Airflow Sensor so no additional wiring to a separate 24DC auxiliary power supply is needed. Setpoints for the two alarms are set with front panel potentiometers adjustable from 0-110% of input span. This is very useful for NAMUR compliant type Airflow Sensors as one of the two alarms can be set at >21mA, indicating a failed transmitter condition per NAMUR standards. Field configurable via selectable jumpers, each alarm function can be site configured for high/low and Failsafe/Non-Failsafe relay action. This fast-acting 50msec response time alarm also comes standard with an adjustable deadband capability of 1-20%. 

Key Attributes

  • Powers and Receives 4-20mA Signal from Airflow Sensor
  • Dual field configurable alarms capable of alarming on
    NAMUR failure output range from Airflow Sensor
  • Relays rated 5A, 250VAC
  • 50msec response time
  • Adjustable deadband for each alarm

 

Download Datasheet

The main production facility for a UK fertilizer company produces ammonium nitrate which is subject to the UK Control of Major Accident Hazards (COMAH) regulations. This organization ensures that businesses take all necessary measures to prevent major accidents involving dangerous substances such as this one and is enforced by the UK Health & Safety Executive (HSE). A review of the emergency shutdown system under IEC61508 Functional Safety Standard revealed an urgent upgrade was needed of electrical, control and instrumentation to satisfy SIL2 System designation.

One of the main areas needing attention was the critical temperature monitoring of the reactor process and the requirement for hardwired alarms on selected Safety Loops because alarms were being generated by a combination of the diverse technology being used and the alarm software of the DCS. Modern safety standards do not allow combining control and shutdown systems in the same DCS.

 Temperature Reactor Alarm Repeat

Download the PDF file 

The Moore Industries STZ and STA were chosen by the company and HSE to provide a hardwired shutdown system meeting the requirements for SIL2 system capability. The highly accurate STZ temperature transmitter features sensor backup and failover capability along with a flexible configuration to accept a range of existing thermocouples. The STA trip alarm, which is the company’s plant standard for SIL hardwired trip alarms, features highly reliable relays and configuration software that is easy-to-use yet robust.

The STZ accurately measures redundant temperature sensors and provides measurement and sensor diagnostics. Should the primary sensor fail, the backup/failover sensor will be transmitted to the STA, Safety Trip Alarm. The STA relays trip when conditions exceed the temperature high and low limits for process safety, triggering an alarm and emergency shutdown. The STA also retransmits its temperature input back to the DCS, via its 4-20mA analog output.

Key attributes:

  • SIL2
  • Sensor Backup/failover of STZ
  • Relay trips

 

Download Datasheet

The quality and effectiveness of pharmaceutical products is critical to the industry and its users. To ensure the quality stays intact, nitrogen is often used for packaging purposes and other processes inside the manufacturing facilities. Because nitrogen is an inert gas, it is often used to exclude or push oxygen out of certain areas, including packages and containers.

Pharmaceutical companies use a method called nitrogen blanketing to protect processes that are used to make their products. Nitrogen blanketing strategies are implemented during production, storage, transportation, and final packaging. Nitrogen blanketing involves adding nitrogen liquid or gas to fill the area between the fill line of a process storage vessel’s content and the top of that vessel. The nitrogen displaces the oxygen inside, which helps ensure that oxygen and moisture don’t contaminate the product or cause a potentially explosive situation due to excess oxygen.

The level of oxygen inside of the Manufacturing Facilities where nitrogen is used must be monitored because the same nitrogen used for oxygen displacement to preserve the valuable contents of the vessel could become deadly to the employees working in the room. Nitrogen leaks can cause the air in the room to become oxygen-deficient, which could cause the employees to suffocate.

Nitrogen Blanketing Application with SPA2 Alarm TripDownload the PDF file

In the above application, an Oxygen Monitor is utilized in conjunction with a Moore Industries SPA2 Programmable Limit Alarm Trip to help avoid this potentially dangerous situation. The Oxygen Monitor provides the oxygen level input to the SPA2 from the inside of the room where the process is occurring. The SPA2 provides two or four independent and individually configurable alarm relay outputs, one of which can be designated to shut off the flow of nitrogen supply when the Oxygen Monitor detects low oxygen in the room; which could be caused by a nitrogen leak in the Process Storage Tank. An E-stop can also be wired in series so that operators can shut off the nitrogen supply manually. The other SPA2 relays can be used to alert employees by being wired to audible and visual warnings. An optional AO analog output on the SPA2 can communicate the Oxygen Monitor readings to a PLC, BPCS or auxiliary safety system.

Key Attributes

  • Programmable input/output parameters and “Universal” DC or AC power input.
  • Two or four independent and individually configurable alarm relay outputs.
  • Optional AO analog output, any range between 0-20mA and 0-10V

Over the past few months, we have been adding more than 1,000 downloadable 3D CAD models for our most popular products to our online catalog. These models are available in multiple file formats for use in the most popular CAD design systems, making it easy to include Moore Industries products in your system designs.

This new feature of the online catalog provides a pop-up 3D viewer that allows you to see different views of the selected product, rotate the model to any viewing angle and zoom in to view detail.  Models can be downloaded and saved for use in 3D CAD systems for inclusion in panel designs and process loop and system designs.

Website 3D CAD Model Screen Capture

The 3D files are compatible for many popular CAD systems including Pro/ENGINEER, Autodesk Inventor, Solidworks, Parasolid, AutoCAD, Catia, IGES, Anvil, CADKey, IronCAD, Mechanical Desktop, ACIS, SDRC I-DEAS, and Unigraphics in 3D formats.IGS, .NEU, .PDF, .SAT, .STP, .X_T, and 2D formats .DWG and .DXF.  Products that feature a 3D CAD model are identified with a “3D View” icon, and a download button is available on each product page.  

Dropping standard product models into a CAD design streamlines the engineering design process, makes it easier for your purchasing team to source the products, simplifies installation and maintenance for the maintenance team, and can shorten lead times for stocking spare products.  Moore Industries Engineering Director Bob Myles commented that “the 3D CAD models will make it much easier for our customers to integrate precise Moore Industries product into their system designs that reduces drawing time, shortening their engineering timeline”.

We’ll continue to add new models with each new product release.

See the available 3D models in the Moore Industries website online catalog

All trademarks, logos and brand names mentioned on this news release are properties of their respective owners.

When a glass recycling division was upgrading one of their recycling facilities from sorting glass 10mm in size (or larger) down to 3mm in size, which provided more business opportunity and diverted more glass from landfills, they looked to Moore Industries 532 Auto/Manual Backup Stations to provide manual backup of their critical Melt Furnace PID control loops. Three panels were fitted with twenty-five 532 Auto/Manual Backup Stations to monitor the host PLC’s PID control for each Melt Furnace chamber. Maintaining temperature control for the Melt Furnaces is paramount and should the primary host controller fail, solidified glass could severely damage and perhaps ruin the furnace. These 532 Auto/Manual Backup Stations were chosen because they can sit passively on the PID control signal from the PLC and if that signal should fail, the 532 automatically generates a control signal based on the last known host PLC value allowing for seamless manual takeover. In addition, during normal operation the 532 allows local operators to quickly switch between Host and Manual control modes when and if required. This provided the recycling facility with the critical redundancy and optional local control that they needed for their Melt Furnaces.

The plant engineers’ control strategy utilized the following strategy:

  • Under normal circumstances, the 532 Auto/Manual Backup Station was left in AUTO mode and allows the 4‐20mA control signal from the PLC to pass straight thru unimpeded to the Melt Furnace’s heating system.
  • If the PLC should fail, the 532 Auto/Manual Backup Station automatically detects this and enters MANUAL mode and maintains the last known output value. This then allows plant operators to manually control the output signal going to the Melt Furnace heating system until the PLC is repaired.
  • Upon failure of the host PLC system, the 532 Auto/Manual Backup Station provides an alarm contact to a local klaxon that alerts plant personnel that they have lost primary host control.
  • If at any time during normal operation the plant operators needed to take manual control, the MANUAL mode button on the 532 allowed them to do so.

Glass Melt ProcessDownload the PDF file

Moore Industries 532 Auto/Manual Backup Station ensures the integrity of your processes with maximum reliability. Isolated inputs and outputs guard against electrical interference, the front face meets NEMA 4X standards for watertight operation, and solid metal housing and sturdy rubber keys enhance durability. The 532 has three bright, crisp vacuum fluorescent digital display areas, with two offering up to nine characters of true alphanumerics. Additional operator-friendly features include custom programmable alarm messages, keys that illuminate when in use and an easy-to-use menu system.

Key Attributes

  • Provides manual backup of critical control loops.
  • Transfers between REMOTE and LOCAL modes via keypad command, digital input, RS-485 communications or loss/return of control signal.
  • Upon keypad command or loss of signal, generates a control signal based on the last known HOST value or preprogrammed value and provides alarm output of signal loss.

Signal isolators are highly economical solutions to common and costly problems that plague many of today’s smart process loops such as ground loop and ambient electromagnetic noise problems. But they do much more than that: they can be used to share and split process signals and even enhance your plant-wide HART investment by also passing valuable HART data to and from your host systems.

HIX HIT Moore IndustriesThe 2-wire (loop powered) HIX or the 4-wire (line-mains powered) HIT enable you to safely share the HART output of one transmitter with a secondary control or recording device. This allows for redundancy without further burden on or risk to a process loop. With up to 1500Vrms of isolation capability, these HART passthrough isolators protect I/O cards from damaging surges, spikes and transients. Employing these HART isolators to loops also breaks the common galvanic path that can pass dangerous overloads from the BPCS or control host to the transmitter or vice-versa– even when the equipment is supposedly “isolated” already.


SST Family Moore IndustriesThe exida-approved, SIL 3 capable 2-wire (loop powered) SSX and 4-wire (line/mains powered) SST Safety Isolators and Splitters are ideal for use in settings where safety is critical. They protect safety systems by isolating an SIS from basic process control or monitoring systems so that disconnections or other failures don’t impact the safety system. They also have 1500Vrms of isolating capability to protect safety I/O cards and systems from surges, spikes and transients in the field. Standard 20V/m RFI and EMI protection stops the harmful effects caused by radio frequencies and electromagnetic interference.

Like the HIX and HIT, the SSX and SST protect and enhance loops and also pass valuable HART data from the field transmitter to host systems and vice-versa. In addition, the SST Splitter model takes the input from one of your process signals and creates two identical, completely isolated outputs to two separate monitoring or control devices. This facilitates maintenance on either output loop without losing the signal on the other output loop. Plus, the optional Loop Maintenance Zener Diode allows the SSX and SST to be removed from the loop for maintenance without interrupting your safety function.

See all of our HART Isolators in the online catalog or contact us for a quote.

Download Datasheet

When the gas metering division for a customer in Malaysia needed a way to provide redundancy and high measurement resolution for their Metering Skids, Moore Industries had the solution with the HES HART to Ethernet Gateway System. The customer’s gas metering application required four HART transmitters to be multidrop wired for communication with two FLOW computers, for redundancy. Their existing system allowed for a multidrop of four HART transmitters back to one flow computer; however, their flow computers did not allow for primary and secondary HART master modes. This meant redundancy was not available to the customer, as only one flow computer was able to see the transmitter measurements. If redundant input cards were wired into the process using HART communication, only one transmitter would be available to send its signal back to the flow computers. As a result, two of the customer’s main requirements for the application could not be met at the same time.

Redundant HART Multidrop Flow Metering Skid

Download the PDF file

Moore Industries HES can be configured as a HART primary or secondary master, capable of having up to 16 HART devices on a multidrop network in a single-channel configuration (64 in a four-channel configuration). With this capability, two HES were able to simultaneously receive the measurements from the four HART transmitters and act as redundant masters. By wiring two redundant flow computers to the two HES through a network switch, the flow computers were also able to simultaneously receive the HART transmitter measurements; this allowed the customer to meet their need for redundancy. In addition, the HES provided the best available resolution for their transmitter measurements via HART communication.

Key Attributes

  • Can be configured as a Primary or Secondary HART Host and polls up to 16 field devices on each of its four channels (total of 64 field devices maximum per HES).
  • High-resolution quality by utilizing HART protocol.
  • Acquisition of both process and diagnostic data from up to 64 smart HART devices for Ethernet-based systems and hosts.

The Moore Industries family of reliable surge suppressors protect your process against failures caused by lightning, power spikes, and other overvoltage damage that can lead to a reduction in measurement accuracy, product quality, and unnecessary/costly shutdowns. Our suppressors ensure the most effective suppression available, providing up to 3kA of surge protection. They are also maintenance and hassle free with easy installation and a safety feature that automatically resets the suppressor after each surge.

Reliable Surge Protectors from Moore IndustriesOur Field-Mount/DIN Mount Surge Suppressor can be placed inside of Moore Industries BH or SB enclosures or mounted on DIN rail. You can use the surge suppressor to protect your HART digital/analog signal lines due to its ability to allow HART signals to pass through. This suppressor exceeds severity level 4 of IEC 61000-4-4 with 3kA/line of surge protection. It is encapsulated and suitable for the harshest industrial environments.

Moore Industries DIN-Plug Surge Suppressor exceeds severity level 4 of IEC 61000-4-4 and 61000-4-5, providing 2.5kA/line of surge protection. The DIN-Plug Surge Suppressor has lightning-fast response time and is designed to fit onto any Moore Industries’ 2-prong terminal block header. This economical, small, and powerful surge suppressor has the suppression technology you need in the field with a compact design that will fit in the most cramped control rooms.

The Data Line Rail-Mount Surge Suppressor is designed to mount on any Top Hat or "G" type DIN-rail for protection of digital signals. It will work with RS-422 and RS-485 communication lines and will ensure that your transmitter and receiver are both protected from overvoltage damage on long communication runs. This unit also exceeds severity Level 4 of IEC 61000-4-4 recommendations, providing sub-nanosecond response time to stop failures.

Download the data sheet or request a quote today

 

 

See More Products

Moore Industries offers a comprehensive line of power supplies to help ensure reliable power goes to all your devices and meets your needs in noise reduction, instrument accuracy, data consistency, and stable communication.

The ECS Economy Power Supply is an ideal process loop component for use with noise prone 2-wire transmitters and data communications equipment, in most cases exceeding performance specifications of higher-priced supplies. The Moore Industries Comprehensive Line of Power SuppliesECS features superior isolation with 2500 Vrms protection so that process signals will not be affected by even severe ground loops, motor noise, or other electrical transients. Though the standard ECS is configured at the factory to 117Vac or 230Vac, it can be field-configured to meet your specific needs.

Moore industries DPS DIN Power Supplies are designed especially for industrial environments and are ideal for powering 2-wire transmitters and data communication modules. The DPS 240 can be used to power a maximum of twelve 4-20mA loops, while the DPS 1200 can power a maximum of sixty 4-20mA loops. Each DPS unit provides complete isolation between the input and output terminals and the unit case, ensuring that power supply fluctuation from line power will not affect instrument accuracy.

The SMP Surface-Mount Power Supply is a compact, precision regulated, linear DC instrument power supply which requires minimal user maintenance and will power large numbers of 2- and 4-wire process instruments. It is the ideal companion to multiple position card racks and rails, or instruments installed in a cabinet or sub-system. The SMP’s superior line and load regulating capabilities help ensure stable signals and that no expensive data loss occurs. All SMPs are designed to operate safely over a temperature range from 0oC to 50oC (+32oF to +122oF) and include full-time short circuit and overload protection to prevent electrical damage to the unit.

View these power supplies in our online catalog and download a data sheet, or request a quote today.

 

 

See More Products

Gathering and communicating critical measurement and diagnostic data in oil and gas applications can be extremely challenging due to the harsh and remote conditions associated with these operations. A company in Kuwait recently needed a way to acquire data from dozens of radar LEVEL transmitters in the field, and in addition, provide power to these transmitters because there were limited power sources available at the site. Moore Industries HES HART to Ethernet Gateway System was able to fulfill both of these requirements. The client multi-dropped six output loop-powered radar level transmitters to each single-channel HES for data acquisition, and utilized the HES transmitter excitation power supply feature to power the transmitters. The gathered process and diagnostic data was then sent over MODBUS/TCP from the HES back to the client’s BPCS (MODBUS/TCP Host) for higher level control, data acquisition and monitoring functions.

HES links ethernet based

Download the PDF file

The HES offers a flexible and economical way to gather process data and instrument diagnostics from smart HART instruments and share it over an Ethernet infrastructure via its embedded web server or with MODBUS/TCP and HART-IP hosts. This enables fast and seamless connectivity for advanced monitoring of critical process variables and parameters. In addition to the single channel configuration outlined above, the HES is also available in a four channel configuration supporting up to 64 HART devices. The HES communicates with all HART 5, 6 and 7 devices including smart valves, multivariable flowmeters, pressure, pH, level, and temperature transmitters and more.

Key Attributes

  • Acquisition of both process and diagnostic data from up to 64 smart HART devices for Ethernet based systems and hosts.
  • FDT/DTM programming, embedded webserver and MODBUS/TCP support seamless connection with all Ethernet based hosts.
  • Embedded power supply supports powering of muti-dopped HART instruments over one twisted pair where power is limited.

     

Download Datasheet

A temperature excursion on the HPump system motor, when discovered in time, can mean that only some minor maintenance is needed. If that same temperature excursion isn’t caught early on, however, components such as front and rear bearings, windings, and thrust bearings can be damaged. Repairs are very costly and could impact production.

Call Moore Industries today or check out the NCS Net Concentrator System datasheet.

Download Datasheet

Moore Industries SPA2 Programmable Limit Alarm Trip is a highly versatile, fast and simple solution to your alarming needs. The SPA2 accepts signal inputs from a wide array of instruments and sensors, provides two or four independent and individually-configurable alarm relay outputs, and its analog output (-AO) option can reduce installation costs and time by providing both alarm and transmitter functions.

Call Moore Industries today at 1-800-999-2900 or download the SPA2 datasheet.

Download Datasheet

A Power Plant in the U.S. Northeast needed to monitor three safety relief valves on gas lines into their power plant. An alarm is required on each valve in case any of these relief valves experience a release of natural gas. Because it would have been too costly to run several new wires out to these valves from the control room PLC, they opted to implement a wireless solution coupled with a field mounted NCS Net Concentrator System.

Gas pipeline Relief Valves Alarm NCS MAA

Download the PDF file

Each relief valve was retrofitted with a WirelessHART positioner/monitor to relay its status back to the WirelessHART gateway. The NCS, acting as a MODBUS RTU Master, gathered the relief valve status from the gateway over RS-485 and provided the local alarming and annunciation. Alarms for each relief valve were quickly configured with easy-to-use web pages within the NCS. If any valve reported a leak, the NCS sent relay outputs to a flashing beacon and a PLC that was tied to the plant’s main SCADA and safety system.    

The alarm function on the NCS system would normally be programmed using its embedded ISaGRAF control engine software, which is very powerful and versatile. However, for this straight forward multi-channel alarming application, they opted to add the –MAA Multipoint Analog Alarm option to the NCS EMM module. This option allows easy to configure alarming with prebuilt web pages that include simple pull-down menus and radio buttons., saving many hours of engineering time.

 

Download Datasheet

Taking advantage of existing HART DATA with minimal expense

Moore Industries’ article on How to Take Advantage of Existing HART Data with Minimal Expense has been published in Process Technology 115, 11.2019 issue (p. 18).  The article points out that although there are 40 million HART instruments installed in the field, making HART the most dominant communications protocol used in process manufacturing facilities across the world,  many existing control and monitoring systems do not support HART communication for 4-20mA devices. HART gateways like the HES fill in this gap, allowing end-users to strategically interface their HART smart devices with their control systems by selecting those devices that add the most value to their operations. The implementation of these HART gateways can be employed as part of the maintenance budget without having to allocate larger capital funds. This can be an affordable way of establishing a plant-floor-to-Ethernet backbone, and integrating valuable HART data into higher layers for further processing and analysis while leaving core automation tasks unaffected.

View Article

Moore Industries Instrument Panels and Systems engineering and design group provides turnkey solutions for your process, automation or Safety Instrumented System (SIS) monitoring and control needs. Moore Industries excels in designing and building compact and modular solutions used to monitor temperature, pressure, level, flow, and safety-related processes with high-performance instrumentation and components.

See the Instrument Panels And Systems in the Online Catalog or Call us at 1-800-999-2900

See More Products

Melt pumps used in polymer production are a special high temp positive displacement pump used at the discharge of an extruder to assure a smooth, high temperature and high pressure (often several thousand psi) supply of the polymer to the filter screen and die for better throughput and uniformity of product. Blockage of the filter screen or die can cause spikes in pressure high enough that the die can be damaged or blown off the feed tap. When that happens, the released polymer will cool and harden at ambient pressure and temperature, requiring hours of cleanup. Downtime costs can be significant.

Polymer Plastics melt pump protection
Download the PDF file

An alarm trip such as the Moore Industries SPA2 in conjunction with an appropriate pressure transmitter can prevent these overpressure failures, saving personnel hours and production losses. The SPA2’s fast response time of  <256msec can trip an alarm fast enough to cut power to the pump motor in time to prevent or minimize damage.

Key Attributes:

  • Fast response
  • Easy set up
  • Independent of the BPCS

 

Download Datasheet

Positive displacement pumps are used where the viscosity of the media is two too high for a centrifugal pump to move the fluid, custody transfer, or where high-pressure discharge is needed. These pumps will rapidly build pressure on the discharge side when the piping is blocked by inadvertent valve closure or other blockages. Damage to the pump, seals, and piping can be catastrophic. Scan time using a pressure transmitter and DCS may be too slow to shut down the pump before damage occurs.

PD pump and Piping protection

Download the PDF file

The best solution is to use a dedicated alarm trip with a fast response time, such as the Moore Industries  SPA2 in conjunction with an appropriate pressure transmitter. The SPA2 continuously monitors pipeline pressure to provide early detection of changes. The SPA2’s fast response time of <256msec can trip an alarm fast enough to initiate valve execution in time to prevent or minimize damage.

Key Attributes:

  • Fast response
  • Easy set up
  • Can be located close to the process pump

 

Download Datasheet

Q: How can I take a HART Primary Variable (PV) from an oxygen transmitter (with only one HART output available), and output two identical analog signals?

A: Here are two approaches you can use by utilizing Moore Industries SST HART Functional Safety Isolator and Splitter or the HIM HART Loop Interface and Monitor.

SST Splitter Solution:

Since the oxygen transmitter has a HART output, we know that this particular output is a 4-20mA signal plus the HART digital signal. We also know that the 4-20mA signal is the HART Primary Variable. Therefore you can wire your oxygen transmitter to the SST Splitter to split the 4-20mA signal and send it to your two destinations as a 4-20mA signal. This is the less expensive approach. The SST solution could also send the HART digital signal to both destinations, if that had value to the user.

SST Oxygen Transmitter

HIM Solution:

Since the O2 transmitter HART output digital signal also contains the Primary Variable, you can wire your oxygen transmitter to the input of the HIM. The HIM will read all the HART Dynamic Variables, but we will assign the Primary Variable to two HIM 4-20mA outputs which go to the two destinations. The HART digital signal does not get passed to the HIM analog outputs.

HIM Oxygen Transmitter

While this is the more expensive strategy, it does offer significantly more flexibility in your system. The HIM can send up to three analog output signals, as opposed to just splitting an analog signal in two; these analog signals can all be the same Primary Variable, or they could be the Second, Third, or Fourth Variables, which are also contained within your oxygen transmitter’s HART output signal. In addition, the HIM can provide you with two relays for Process or Diagnostic alarming and has a large 5-digit display for ease of use. Because the HIM is a configurable device it can easily be repurposed in the future.

Do you want more information? Download the data sheet. Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.

Problem: We have several tank farms in the field where we need to monitor the tank level. Our remote I/O has failed in the past due to high ambient temperature conditions of 122°F (50°C). Is there a field I/O system that can handle these extreme conditions and can also communicate with my plant-standard Allen-Bradley PLCs?

Interface with AB PLCs in High Ambient Temperatures Problem Solvers Moore Industries
Download the PDF file

Solution: Able to handle even the most extreme ambient temperature conditions, the NCS NET Concentrator System® operates in ambient temperature ranges of up to 185°F (85°C). Using a ProLinx Modbus/TCP-to-Ethernet/IP communication gateway, you can take all of your field signals from the harsh environments and transmit them back to your Allen-Bradley PLC on the plant’s existing Ethernet network. In addition, the NCS isolates the signals to prevent ground loops and can supply loop power to each of your 2-wire level transmitters.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]

Problem: We have a DeltaV control system and have remote areas where the ambient temperature gets above 65°C (150°F). The DeltaV remote I/O will not operate at ambient temperatures that high. Currently we have spare twisted pairs leading from the remote areas to our control room where the DeltaV is located. Do you have any remote I/O that communicates with DeltaV via twisted pair and has temperature specifications that exceed 65°C (150°F)?

Interface Transmitter Signals to DeltaV Over MODBUS Problem Solvers Moore Industries

Download the PDF file

Solution: The NCS NET Concentrator System® product family provides the provision for communicating via MODBUS RTU. The NCS gathers data from our universal I/O modules and sends the data out over a RS-485 MODBUS RTU port. All of our I/O modules operate from –40°C (–40°F) to +85°C (+185°F). For critical applications, the NCS features the provision for redundant communications links.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]

Problem: We have an old transmitter in our remote pump station that we want to interface with our PLC. We found two problems: The field signal is 0-10V and the PLC accepts only 4-20mA. The pump house uses electrically noisy motors that can interfere with the PLC.

Field Configurable Converter Blocks RFI Problem Solvers Moore Industrie
Download the PDF file

Solution: Add the 4-wire FCT FieldProgrammable Signal Converter. It accepts a wide variety of inputs and provides a proportional, isolated 4-20mA output to the PLC. When specified with the -RF option, the FCT provides 30V/m RFI/EMI protection.

Model Number Example
FCT / PRG / PRG / U / -RF [DIN]

Problem: We need to implement several temperature related Safety Instrumented Functions (SIF) in multiple areas throughout our plant. The SIF needs to be IEC 61511 compliant and involves a Logic Solver, Sensor and Final Control Element.

Using the STA as a Single Loop Logic Solver Problem Solvers Moore Industries

Download the PDF file

Solution: The SIL 2/3-capable STA Safety Trip Alarm can be used as an effective yet affordable Single Loop Logic Solver to slam shut or open a valve to mitigate a dangerous process condition. Additionally, the STA can retransmit the temperature signal to a Basic Process Control System for additional monitoring or control purposes.

Model Number Example
STA / TPRG / 3PRG / 24DC / -AO [DIN]

Problem: I need a reliable and dependable DIN rail mount temperature transmitter with a display that can work in my SIL 2 Safety Instrumented System (SIS).

Using the STA as a SIL 2 Temperature Transmitter Problem Solvers Moore Industries
Download the PDF file

Solution: The exida-approved SIL 2/3-capable STA Safety Trip Alarm can be used as a temperature transmitter when the safety shutdown system needs to closely monitor temperature signals throughout the plant. Local indication and two alarm contacts are standard included options. Additionally, a FMEDA report is available that includes all of the relevant safety data.

Model Number Example
STA / TPRG / 3PRG / 24DC / -AO [DIN]

Problem: In our manufacturing plant, we can’t identify peak demand periods so we’re paying higher electrical rates than necessary.

Save Money by Monitoring Peak Demand problem Solvers Moore Industries
Download the PDF file

Solution: It’s a common policy for electrical utilities to charge higher rates during peak periods. Analyze data from our PWT Watt Transducer to find out when peak demands occur and shed non-vital loads at those times. Load shedding allows you to shutdown when rates are high and reschedule work accordingly.

Model Number Example
PWT / 120AC, 5A / 4-20MA / 3E / -120AC [DM]

Problem: We need to track power usage on our motor for efficiency calculations and preventative maintenance schedules. Any ideas on how to accurately bring back this information to our PLC?

Monitoring Motor Power Consumption Problem Solvers Moore Industries
Download the PDF file

Solution: The PWT AC Power Transducer can do exactly what you need. The PWT accepts both voltage and current inputs and provides a 4-20mA signal proportional to watts or kilowatts for direct interface with your PLC.

Model Number Example
PWT / 120AC, 5A / 4-20MA / 3E / -120AC

Problem: We have several motors that drive mixers. We realized that the motor current increases when the proper batch consistency is reached. We would like to monitor this current in our DCS. What do you suggest?

Blending Consistency Monitoring Problem Solvers Moore Industries
Download the PDF file

Solution: Use our PAC AC Current Transducer. It will accept the input from the CT on your pump motor and provide a proportional 4-20mA signal to your DCS.

Model Number Example
PAC / 5A / 4-20MA / S / -120AC [SM]

Problem: How can I sample HART data from a smart instrument without affecting normal loop operation?

Use HIM in Listen Mode to Sample HART Data Problem Solvers Moore Industries
Download the PDF file 

Solution: Use the HIM in “Listen” Mode to passively connect it to a loop. This allows it to be added to a loop with a Primary or Secondary HART Master without assuming the role of a Master because it connects passively without assuming the role of the a Master. In “Listen” Mode, the HIM continuously samples HART data from a smart instrument without affecting normal loop operation.

Model Number Example
HIX / 4-20mA / 4-20mA / 12-42DC [DIN]

Problem: I need to test the emergency shutdown valves at my plant, but don’t want to disrupt our processes by having to close the valves.

Reducing Process Disruption in On Line ESD Valve Testing Problem Solvers Moore Industries
Download the PDF file

Solution: The HIM can verify that a valve is operational without having to follow the standard procedure of completely closing the valve. A logic solver such as a DCS or PLC can send a 90 percent signal to the valve, with the HIM serving as an alarm trip when the valve reaches 90 percent. A second HIM relay trip set to 100 percent verifies that the valve reopened after the test. Because the valve was only momentarily closed and immediately reopened, the process flow is relatively unimpeded and process disruption is kept to a minimum.

Model Number Example
HIM / HART / 2AO / 24DC / -2PRG [DIN]

Problem: The secondary variable in my multivariable transmitter is temperature. My process temperature is very dynamic and I need to alert the operators when my temperature becomes unstable. I would like to alarm at two different points.

Multi Level Alarming for a Single Process Variable Problem Solvers Moore Industries
Download the PDF file

Solution: This is easily accomplished with the HIM Smart HART Loop Interface and Monitor. Either of its two alarm channels can be configured to trip at any value of the HART variable, including process temperature, mass flow, hydrostatic levels and differential pressure.

Model Number Example
HIM / HART / 2AO / 24DC / -2PRG [DIN]

Problem: We need a cost-effective, high-density HART multiplexer that will pass the 4-20mA loop to our control equipment and read the HART data, outputting it via RS-485 or Ethernet. It also needs to take up as little panel space as possible.

HART Multiplexers That Maximize Space Problem Solvers Moore Industries
Download the PDF file

Solution: The HCS connects in parallel to the HART signal, allowing it to pass to the control equipment. If you are using HART devices connected in a multidrop loop, you can interface all of the HART devices in the loop to a single HCS. The HCS is only 1” wide, so a group of eight takes up less than one foot of DINrail width.

Model Number Example
HCS/HART/MB485/9-30DC [DIN]

Problem: I just installed a new HART smart pH transmitter. It has great diagnostics but they are only accessible using the handheld communicator. Is there a way to get this information in real time?

HART pH Transmitter Interface to Control Room Problem Solvers Moore Industries
Download the PDF file

Solution: Connect the HIM across the pH signal wires at the back of the panel. It can be configured to monitor the various HART data diagnostic bits and to alarm on out-ofnormal conditions of the sensor. You can even set the 4-20mA output to represent the process temperature or the sensor output.

Model Number Example
HIM / HART / 3AO / 24DC / -2PRG [DIN]

Problem: Sometimes, external influences can cause errors in the 4-20mA signal from my HART transmitters. On a critical loop, I end up with costly product loss. I can use redundant transmitters, but that has its own set of complications. Are there any other options?

Digital Signal Unaffected by Analog Errors Problem Solvers Moore IndustriesDownload the PDF file

Solution: The HIM Smart HART Loop Interface and Monitor reads only the digital data and is unaffected by the 4-20mA errors. Assign the HIM output to the primary variable. Let the DCS compare this signal to the transmitter signal and, if they don’t agree, set an alarm to fix the problem before production is lost.

Model Number Example
HIM / HART / 2AO / 24DC [DIN]

Problem: We have an existing gauging system in our tank farm consisting of a temperature transmitter and a level transmitter for each tank with a 4-20mA connection to a DCS. We are planning to modify the system to include an HMI in a new location for a tank gauging system to monitor 250 tanks. How can we get the information from our existing sensors to the new HMI separately from the DCS?

Connecting HMI to Tank Gauge Sensors Problem Solvers Moore Industries
Download the PDF file

Solution: The HCS HART® Concentrator System will allow you to interface your HART signals directly with MODBUS-based control systems such as an HMI. This will allow you to connect a new HMI without disturbing an existing DCS. If the level and temperature is connected via a HART loop to the DCS, you will need to have two HCS units connected to each loop in order for the system to work.

Model Number Example
HCS / HART / MB485 / 9-30DC [DIN]

Problem: I need to interface multiple HART flowmeters to a DCS with a MODBUS interface. Do you have a solution for this?

Connecting a HART Device to a DCS With MODBUS Problem Solvers Moore Industries
Download the PDF file

Solution: Connect one HART device in single drop mode or up to 16 HART devices in multidrop mode to our HCS HART-to-MODBUS interface module. The HCS queries the HART devices and stores the data internally in MODBUS registers. Your DCS MODBUS card serves as the MODBUS master, querying the HCS to grab the data.

Model Number Example
HCS / HART / MB485 / 9-30DC / -RF [DIN]

Problem: Our non-HART DCS can only read the primary variable signal from our multivariable transmitter but I would like to monitor the other information in the HART signal.

Break Out Analog Signals with the HIM Problem Solvers Moore Industries
Download the PDF file

Solution: The HIM Smart HART loop interface and monitor connects in the control room and provides a 4-20mA output representing any one of the other HART variables. Its two relays can be set to alarm on an out-of-range condition for any of the variables.

Model Number Example
HIM / HART / 3AO / 24DC / -2PRG [DIN]

Problem: We have a couple of critical 4-20mA signals in remote locations that need to be brought into our DCS for trending and alarming. These signals are critical to our day-to-day production schedules. Can the NET ConcentratorSystem® be used with the fiber backbones that are already in place?

Utilize Fiber Links for Critical Remote Signals Problem Solvers Moore Industries
Download the PDF file

Solution: By implementing fiber switches, a redundant fiber ring can be established between the remote locations and the control room. The NCS can then accept the 4-20mA signals from the field and transport them via fiber to the control room where they are converted by the NCS back to the original 4-20mA signals.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
AOM / IO / AO4 / IP [DIN]

Problem: We have several dispersed locations throughout the county where we need to access fluid levels and pump parameters at lift stations. Do you have a solution that can be remotely installed to monitor analog and discrete signals and then transmit them via a wireless data link?

Transfer Critical Signals Over a Wireless Data Link Problem Solvers Moore Industries
Download the PDF file

Solution: Use the NCS NET Concentrator System to collect the analog and discrete signals from the dispersed lift stations. Then use our WNM Wireless Network Module to send the data over a wireless network back to the control system. At the opposite end of the data link, an NCS station collects the data from the Wireless Network Module, and then re-create the original analog and discrete signals for direct input into your control system.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]
AOM / IO / AO4 / IP [DIN]
ROM / IO / RNO8 / IP [DIN]

Problem: We’ve added a small boiler on the far side of the plant and we would like to historically trend the steam temperature profiles with our DCS historian. There are plenty of spare 4-20mA inputs on our DCS. Unfortunately, we have run out of twisted wire pairs to get the signals from the field to the DCS. We do, however, have a newly-installed Ethernet backbone. Do you have a way to convert the temperature sensor signals to Ethernet, and then convert the signals from Ethernet to 4-20mA signals for our DCS input cards?

Temperature Sensor to Ethernet to Analog Signal Conversion Problem Solvers Moore Industries
Download the PDF file

Solution: Our NCS NET Concentrator System® allows sensor inputs to be converted to a digital signal and then transmitted over Ethernet. Using our channel-mapping capabilities enabled by the ISaGRAF Control Engine Software, any input channel can be assigned to any output channel in the network. In this application, the NCS essentially becomes an Ethernet temperature transmitter.

Model Number Examples
EMM / COM / SM / 20-30DC
TIM / IO / TI4 / IP [DIN]
AOM / IO / AO4 / IP [DIN]

Problem: We have added a small mixing tank on the far side of the plant and we would like to montior the temperature transmitters with our DCS. There are plenty of spare 4-20mA inputs on our DCS. However, we have run out of spare twisted pair to get the analog signals back to them. We do have an Ethernet backbone. Do you have a product that can accept 4-20mA signals at the field location and transmit those signals via Ethernet to another module that can convert the signals back to 4-20mA?

Peer to Peer Distributed IO Network Over Ethernet Problem Solvers Moore Industries
Download the PDF file

Solution: Our NCS NET Concentrator System® accepts the 4-20mA signals and converts them into digital form that can be transmitted on the Ethernet backbone. At the opposite end of the data link, the NCS converts the digital signal back to identical representations of the original 4-20mA signals for direct input to the DCS analog input cards. Using this, you won’t have to install new twisted pair wiring.

Model Number Examples
EMM / COM / SM / 20-30VDC [DIN]
AIM / IO / TI4 / IP [DIN]
AOM / IO / TO4 / IP [DIN]

Problem: We have seven signals in one remote location and eight in another that we want to bring into our existing PLC control system. Do you have a remote I/O product that can be placed on a twisted pair and digitally bring signals back to the MODBUS RTU port on our PLC?

Peer to Host Data Collection Over Twisted Pair Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET Concentrator System® allows any mix of analog, temperature (RTD and thermocouple) and discrete inputs and outputs in a network. Data can be sent via MODBUS RTU HOST. You can daisy chain up to 255 NCS slaves onto this network. The NCS also has an OPC server available for those host systems that don’t support MODBUS RTU.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: We have dispersed locations in the field with each having eight to 10 signals that we want to bring into our existing HMI SCADA system. Do you have a remote I/O product that can be placed throughout the plant and communication with our HMI via our Ethernet backbone?

Peer to Host Data Collection Over Ethernet Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET Concentrator System® allows any mix of analog, temperature (RTD and thermocouple) and discrete inputs and outputs in a network. Data can be sent via Ethernet to your HMI. The NCS supports OPC and MODBUS/TCP protocols, which are both supported by all HMI strategies.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: During a shakedown for a new control system, we discovered that 42 signals from the hydrocracker had developed ground loops. Do I have to buy 42 isolators to fix it?

Multiple Ground Loops Plague Oil Refinery Problem Solvers Moore Industries
Download the PDF file

Solution: Just 3 CCS Cable Concentrator Systems can do the same job for up to 48 signals. The CCS isolates each field signal, concentrates it onto a twisted wire pair with up to 127 other signals, and transmits it back to the DCS using MODBUS RTU protocol. The CCS network also frees up wires in your multi-core cables.

Model Number Example
IMM / U / RS485 / 18-30DC / –MBR [DIN]

Problem: We have remote storage locations scattered throughout the country that store inventory. Our service engineers would like to check the critical temperature and other measurements at the remote locations as they travel. Unfortunately, we only have analog telephone lines at each location. Do you have a solution that would enable them to use their laptops to check the temperature from anywhere?

Monitoring Remote IO Sites Over Telephone Lines Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET ConcentratorSystem® collects any combination of temperature, analog and discrete signals at the remote sites. It feeds them to an Ethernet telephone modem, which transfers the signals any distance back to a PC equipped with an analog telephone modem. Since the NCS has an embedded web server, the status of all of these signals can be viewed with any PC over an intranet or the internet using Internet Explorer™. The NCS even provides data logging for historical collection of the dispersed process data.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
TIM / IO / TI4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: The EPA requires us to log flow and temperature data from our smoke stacks. Currently we are using a historian package called Pi from a company called OSI. Since these signals are not used for control, we really don’t want to take them to our expensive I/O cards in our DCS. Do you offer cost-competitive I/O that could connect to our historian over our plant Ethernet backbone?

Interface with OSI Pi Historian Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET Concentrator System®, as standard, provides the provision to communicate over Ethernet. The NCS gathers data from our universal I/O modules and sends that data over 10/100Base-T Ethernet. It supports OPC and MODBUS/TCP. We offer an OPC server for the NCS that can be loaded on any PC or Windowsbased workstation. The OSI Pi Historian has an OPC client interface that allows collection of these monitoring points. Pi Historian also supports MODBUS/TCP.

Model Number Examples:
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]

Problem: We have various process signals in remote locations that we want to bring into our existing control system which operates on a 4-wire MODBUS network. Do you have remote I/O that can communicate via 4-wire MODBUS?

Interface with 4 Wire MODBUS RTU Control Systems Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET ConcentratorSystem® allows any mix of analog, temperature (RTD and thermocouple) and discrete inputs and outputs in a network. The NCS converts the signals to a standard MODBUS RTU communications protocol (RS-485), which can be sent long distances back to the 4-wire control system. An RS-485 Isolator/Repeater, such as the one offered by B&B Electronics, is used to convert the NCS’s 2-wire RS-485 to the 4-wire RS-485 required by the control system. MODBUS RTU works fine over both 2- and 4-wire RS-485 networks.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AO4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: We have just updated our plant with a new DeltaV control system. We have discovered that there are a few locations where we would like to have access to additional temperature and pressure points for alarming in the DeltaV Alarm Manager. However, we cannot justify the high cost of installing DeltaV I/O for just a few points. Do you offer any cost-effective I/O solutions that could connect to our DeltaV over our existing plant Ethernet backbone?

Interface Transmitter Signals to DeltaV Over Ethernet Problem Solvers Moore Industries
Download the PDF file

Solution: Use the NCS NET Concentrator System® to gather data from the additional monitoring sites and send the data back to the DCS over the existing 10/100Base-T Ethernet backbone. The NCS is available with an OPC server that can be loaded onto any PC or the DeltaV workstation. Since DeltaV supports OPC, you can use our more affordable NCS I/O as a front end to the alarm manager software.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]

Problem: There are points within our plant that we manually log once per day. Because they are scattered throughout the plant, it is very time-consuming for one person to cover all of these locations. Since we aren’t controlling these points, is there a way that we could inexpensively monitor them from one central location?

Data Monitoring Using Internet Explorer Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET Concentrator System® with an Ethernet Interface Module (EIM) features an embedded web browser. From any PC that has Internet Explorer installed, you can instantly view all process data points that are connected to the NCS. The NCS also has a built-in data logger that can be used for historical archiving should the remote PC lose communication with the measurement points.

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: We need to send large numbers of process signals from our remote processing plant back to our main control room. We are looking for an economical remote I/O solution that can communicate over a radio link.

Concentrate Signals to Reduce Wiring Costs Problem Solvers Moore Industries
Download the PDF file

Solution: Our NCS NET Concentrator System® will accommodate both high level and low level signals for input and output and is modularly expandable to thousands of channels. It can communicate over radios, telephone modems, fiber optic or direct wire using Ethernet and MODBUS RTU protocols directly to your DCS or PCbased SCADA system.

Model Number Examples
EMM / COM / DM / 20-30DC [DIN]
TIM / IO / TI4 / IP [DIN]
AOM / IO / AO4 / IP [DIN]
DIM / IO / CC8 / IP [DIN]

Problem: We have remote compressor stations throughout the plant that are currently monitored by antiquated analog gauges and meters. We would like to upgrade to a rugged field I/O that can monitor 4-20mA signals from temperature and pressure transmitters and send the data back via MODBUS RTU over an in-place twisted pair. Ideally, we would like a redundant network so we can take data to both a remote monitoring cabinet and to our new DCS historian. Do you have a I/O system that can handle this?

Compressor Station Monitoring Using Redundant MODBUS Problem Solvers Moore Industries
Download the PDF file

Solution: The NCS NET ConcentratorSystem® allows you to build a MODBUS RTU remote I/O network that can simultaneously communicate with two independent MODBUS masters. Any combination of input and output I/O modules can then be added, or expanded, to monitor the various remote points. To accommodate mounting at the compressor sites, the NCS operates at ambient temperature ranges of -40°C to +85°C (-40°F to +185°F).

Model Number Examples
EMM / COM / SM / 20-30DC [DIN]
AIM / IO / AI4 / IP [DIN]

Problem: We need to use the output from one temperature transmitter from the process to control two valves...one for the heating system and one for the cooling system.

Split Range Valve Control Problem Solvers Moore Industries
Download the PDF file

Solution: Use two IPH2 transmitters in conjunction with our SIY PCProgrammable Signal Isolator Converters to control the valves. One SIY configured for 12-4mA (reversed) and the other for 12- 20mA. At 12mA the setpoint is satisfied and both valves are closed.

Model Number Example
SIY / PRG / 4-20MA / 10-42DC [DIN]
IPH2 / 4-20MA / 3-27PSIG / 35PSI /-FR1 [WDNA]

Problem: We are upgrading our brewery to a centralized DCS and eliminating pneumatic controllers. Our flow transmitters are working great and they’re staying. How can we cut the cost of running pneumatic tubing to the DCS?

Save Money By Replacing Pneumatic Tubing Problem Solvers Moore Industries
Download the PDF file

Solution: Install a PIH Pressure-toCurrent transmitter next to your flow transmitter. This enables you to replace most of the tubing with a less costly twisted-wire pair for sending information to the DCS. Installing an IPH2 Current-toPressure Transmitter next to your DCS will cut your tubing costs from the DCS to your pneumatic control valve.

Model Number Example
PIH / 3-15PSIG / 4-20MA / 12-42DC [WDNS]
IPH2 / 4-20MA / 3-15PSIG / 20PSI / -FR1 [WDNS]

Problem: Vibration from the valves on my offshore oil rig is causing very jumpy valve operation on my existing I/Ps. I’m looking for an I/P converter that can accurately regulate the valve and withstand high vibration.

IP Conversion in High Vibration Environments Problem Solvers Moore Industries
Download the PDF file

Solution: For precise pipeline valve regulation, look to our IPX Explosion-Proof Field-Mount I/P Transmitter. It converts a 4-20mA signal to a proportional 3-15psig for stable pneumatic valve control. It features NEMA 4X and IP65 ratings and operates flawlessly even when mounted next to a valve or other highvibration equipment.

Model Number Example
IPX / 4-20MA / 3-15PSIG / 20PSI [EXIP]

Problem: To complete the upgrade of our processing line, we must transmit twice as many pneumatic signals. We must add 32 I/Ps and 16 P/Is to the control panel but have a very limited amount of space.

Crowded Pneumatic Cabinet Needs More Signals Problem Solvers Moore Industrie
Download the PDF file

Solution: Our slim IPT2 and PIT pneumatic transducers provide superior performance in limited space. Up to eight IPT2 s or 12 PITs fit on one foot of DIN rail. All 48 of your units will fit easily into a 36”x36”x8” enclosure.

Model Number Example
IPT2 / 4-20MA / 3-15PSIG / 20PSI / -FA1 [DIN]
PIT / 3-15PSIG / 4-20MA / 12-42DC / -RTB [DIN]

Problem: We would like to monitor the three phases of power sourcing the main process motor and send an alarm if there is a power loss on any leg of the phase.

Warn of Power Loss to Process Motor Problem Solvers Moore Industries
Download the PDF file

Solution: Connect the 0-5AAC signal from the CT on each phase of the motor to an ECA. The ECA will provide a relay output when the current in its phase drops below a predetermined value. This will alert the technicians to an imbalance or failure of one of the phases.

Model Number Example
ECA / 0-5AAC / DH1L1 / 24DC [DIN]

Problem: We’re replacing the pressure switch with a pressure transmitter on our holding tank. Can we take the 4-20mA signal and use it for our emergency shutdown system AND for trending at the DCS?

Use One Process Signal for Two Different Tasks Problem Solvers Moore Industries
Download the PDF file

Solution: Absolutely, the SPA2 Programmable Alarm provides both emergency shutdown capability and an isolated 4-20mA retransmission of the pressure signal for trending in the DCS. The SPA2 also provides a local indication of the pressure and relay status indicators.

Model Number Example
SPA2 / HLPRG / 1PRG / U /-AO [DIN]

Problem: I want to use a single device to provide local indication of temperature, alarm and shutdown relays. I also need to send an isolated 4-20mA signal to my DCS for the same temperature. Can I use the same device for all of these functions?

Shutdown System Needed at Refinery Problem Solvers Moore Industries
Download the PDF file

Solution: Yes! The SPA2 Programmable Alarm Trip that takes temperature sensor inputs (-TPRG) provides all of these functions in a single instrument. In fact, you can even set one of the relays to alert you to a failed sensor without initiating an alarm or shutdown. The SPA2 can be supplied in our NEMA 4X R-BOX enclosure for field mounting.

Model Number Example
SPA2 / TPRG / 4PRG / U / -AO [DIN]

Problem: I need a low pressure alarm on my instrument air system, but I can’t afford to have a system shutdown if the pressure transmitter fails and the header pressure is still acceptable. I also want to use the signal for monitoring in the Control Room.

Open Circuit Detection for 4 20mA Input Problem Solvers Moore Industries
Download the PDF file

Solution: A SPA2 Programmable Alarm with a dual relay and analog output will do the job. Set Relay 1 with a time delay to close when the header pressure falls below an acceptable level and Relay 2 to open if the pressure transmitter fails so a shutdown will not occur.

Model Number Example
SPA2 / HLPRG / 2PRG / U / -AO [DIN]

Problem: We upgraded to a DCS with alarms programmed directly into the software, but our insurance company requires a hard alarm backup. Is that standard operating procedure?

Hard Alarm Required for Insurance Policy Problem Solvers Moore Industries
Download the PDF file

Solution: Yes! Many plants are adopting the new standards that require redundant alarm devices... especially for critical loops or processes. We supply systems with varying levels of redundancy dependant on how critical the application. Safety Instrumented Systems may be designed modularly to meet most any requirement.

Model Number Example
SPA2 / HLPRG / 4PRG / U / -AO [DIN]

Problem: We use 3 K-type T/Cs to monitor the burn-off flame of our emissions flare stack. However, when the wind blows, the flame leaning away from the stack gives a false out.

Flare Stack Burn Out Problem Solvers Moore Industries
Download the PDF file

Solution: Change your strategy to rely on low readings from two T/Cs to indicate no flame in a 2-out-of-3 voting scheme. This ladder rung approach creates a “flame out circuit” ONLY in the event that two of the three alarms are tripped. The SPA2 Programmable Alarm Trip’s time delay capability also helps prevent false trips.

Model Number Example
SPA2 / TPRG / 2PRG / U / -DPDT [DIN]

Our loop requires two alarms: one to warn the control room and a second for emergency shutdown. Is there an inexpensive way to accomplish this?

Dual Alarm Warns Prior to Full Shutdown Problem Solvers Moore Industries
Download the PDF file

Absolutely. Our SPA2 Programmable Alarm Trip with two relays accepts the 4-20mA input from your transmitter then provides two relay outputs to your DCS... one for warning and the other for shutdown. Industry-best RFI protection and FM Class I, Div 2 approvals make the SPA2 a great field fit for field locations too.

Model Number Example
SPA2 / HLPRG / 2PRG / U [DIN]

Problem: We have a pump doing heavy labor on our tank farm. In the past the bearings have overheated and caused the complete failure. How can we avoid future problems?

Avoid Motor Damage from Overheated Bearings Problem Solvers Moore Industries
Download the PDF file

Solution: Use an ALX Alarm linked to a TDY Temperature Transmitter. When the bearings get too hot, the ALX will alarm and switch off power to the motor. After a cooling-off period, the ALX resets automatically, requiring little manual intervention once installed.

Model Number Example
ALX / 4-20MA / H1 / 6.3VLP [BH2NS]
TDY / PRG / 4-20MA /10-42DC [BH2NG]

Problem: We just lost a DCS input card due to a transient spike hitting our loop wiring and creating a damaging voltage surge to the input of the DCS.

Safeguard Expensive IO Cards from Overloading Problem Solvers Moore Industries
Download the PDF file

Solution: Stay clear of transients, surges and spikes with the HIX HART® Isolator. It provides isolation while “passing through” both the analog 4-20mA and HART digital signal undisturbed.

Model Number Example
HIX / 4-20MA / 4-20MA / 12-42DC [DIN]

Problem: We need to transmit data from a Smart HART transmitter to both a primary DCS and an emergency shutdown device. Can we do this without placing a further burden on our process loop?

Monitoring and Powering a 2 Wire Transmitter Problem Solvers Moore Industries
Download the PDF file

Solution: Use the 2-wire HIX HART Isolator to safely share a HART signal between two receiving devices. It sends fully-isolated instrument loops to both the primary DCS and a secondary HART master (such as an emergency shutdown device). This allows for redundancy without taxing the process loop.

Model Number Example
HIX / 4-20mA / 4-20mA / 12-42DC [DIN]

Problem: We’re experiencing signal drift between the 4-wire field transmitter and the grounded receiver on our newly commissioned loop. What’s causing this problem?

Stop Ground Loops Problem Solvers Moore Industries
Download the PDF file

Solution: The difference in potentials between two grounded, non-isolated devices may result in a ground loop. Installing an SIY or ECT to break the galvanic path prevents the effects of ground loops, motor noise and electrical interference.

Model Number Example
SIY / PRG / 4-20MA / 10-42DC [DIN]
ECT / 4-20MA / 4-20MA / 12-42DC [DIN]

Problem: Even with a current transformer, a dangerous 0-5 amp AC signal enters our instrument cabinet. We would like to keep power levels in a safer range for our instrument technicians.

Step Down Unsafe High Level Signals Problem Solvers Moore Industries
Download the PDF file

Solution: Install an ECT with the -EM option. It provides a “mini” external input transformer to step down the 0-5 amp signal to a lowlevel 0-5mA signal into the ECT. The ECT then transmits a 4-20mA signal to the receiving instrument. This permits safe servicing without disconnecting the main CT.

Model Number Example
ECT / 0-5AAC / 4-20MA / 12-42DC / -EM [DIN]

Problem: We need to use the output from one temperature transmitter from the process to control two valves...one for the heating system and one for the cooling system.

Split Range Valve Control Problem Solvers Moore Industries
Download the PDF file

Solution: Use two IPH2 transmitters in conjunction with our SIY PCProgrammable Signal Isolator Converters to control the valves. One SIY configured for 12-4mA (reversed) and the other for 12- 20mA. At 12mA the setpoint is satisfied and both valves are closed.

Model Number Example
SIY / PRG / 4-20MA / 10-42DC [DIN]
IPH2 / 4-20MA / 3-27PSIG / 35PSI /-FR1 [WDNA]

Problem: For a custody transfer application, we need to monitor the input from a field flow transmitter at two locations simultaneously. What’s our easiest option?

Share a Process Signal at Two Locations Problem Solvers Moore Industries
Download the PDF file

Solution: The dual-output ECT signal splitter takes the input from one transmitter and sends two identical isolated outputs to two receiving devices for monitoring, recording or control.

Model Number Example
ECT / 1-5V / 2X4-20MA / 24DC [DIN]

Problem: I use PLCs to control Variable Frequency Drives (VFD) in my process, but routinely have problems with feedback noise affecting the output card.

RFI Plagues Variable Frequency Driver Problem Solvers Moore Industries
Download the PDF file

Solution: Place an input looppowered isolator like our SCX into the loop. No dedicated power supply is necessary and when ordered with the -RF option, the SCX ends noise problems with 50 V/m of protection for your PLC input cards.

Problem: We have several loops where we need to use 4-wire transmitters connected to a DCS. However, the DCS is powering its input loops, causing a conflict with the powered transmitters.

Put an End to Bucking Power Supplies Problem Solvers Moore Industries
Download the PDF file

Solution: Installing an ECT will quickly put an end to your “bucking” power supplies. The ECT operates with powered inputs from both sides, restoring normal loop operations.

Model Number Example
ECT / 4-20MA / 4-20MA / 12-42DC [DIN]

Problem: The signal from our field transmitter is sent to both our DCS and a PLC in a remote area. The trouble is that disconnecting the leads at the PLC results in a loss of signal to both.

Protect Your Loop with Area Isolation Problem Solvers Moore Industries
Download the PDF file

Solution: Installing a buffer, like the SIY PC-Programmable Signal Isolator, prevents a failure at the PLC from propagating to the DCS. It also breaks the common galvanic path, effectively eliminating development of a ground loop.

Model Number Example
SIY / PRG / 4-20MA / 10-42DC [DIN]

Problem: We have a project to expand our plant that includes monitoring of many non-isolated process signals. We’re looking for high-density DIN mounting, low cost and high performance.

 

One Isolator Can Take the Place of Two Problem Solvers Moore Industries
Download the PDF file

Solution: The dual-channel ECT offers two independent, high performance isolation channels in one enclosure. The pricing, high density mounting capability and simplified wiring add up to big savings for your application.

Model Number Example
ECT / 2X4-20MA / 2X4-20MA / 117AC / -TX [DIN]

Problem: Our compressor station uses a 24Vdc battery as the primary source for powering process instruments. We’d like to monitor the battery voltage levels back at the control room...any suggestions?

Monitoring Battery Voltage Problem Solvers Moore Industries
Download the PDF file

Solution: One way is to use our SIX Signal Isolator. It accepts the battery voltage as an input and provides a proportional 4-20mA output signal to the DCS for monitoring.

Model Number Example
SIX / 0-30V / 4-20MA / 12-42DC / - ATL [DIN]

Problem: We upgraded to new HART smart field transmitters but are still using our original field mounted isolators. Now we can’t access the HART transmitters from the control room. Is there a solution?

 

Isolator Passes HART Digital Signal Problem Solvers Moore Industries
Download the PDF file

Solution: Our HIX HART® Isolator offers full isolation and complete HART communication capabilities. • HART signal “passes” through • Get status at any termination point • One HART signal can be used by both the primary and secondary masters.

Model Number Example
HIX / 4-20MA / 4-20MA / 12-42DC [DIN]

Problem: We have a ground loop problem between an old 4-wire field transmitter and our PLC. We want to install an isolator to break the galvanic path, but the PLC can’t power the loop and we don’t want to buy another power supply. Can you help?

Isolator Gets Power From the Input Side of Loop Problem Solvers Moore Industries
Download the PDF file

Solution: Definitely! The 2-wire, inputloop powered ECT gets its operating power from its input side. You can power it from the 4-wire transmitter without adding a power supply.

Model Number Example
SCX / 4-20MA / 4-20MA / 5.5VLP [DIN]

Problem: After installing several HART smart field devices into our process, we found the HART FSK signal was being interpreted by the DCS as noise and causing control upsets. We want to utilize the benefits of HART but can’t tolerate the upsets!

HART Signal Interference Problem Solvers Moore Industries
Download the PDF file

Solution: Choose our ECT, FCT, or SIY to serve as “HART Stoppers”. They pass the 4-20mA but block the FSK signal to the DCS. When mounted in the control room, access to the HART signal can still be accomplished on the input side to utilize the HART benefits you had expected.

Model Number Example
ECT / 4-20MA / 4-20MA / 12-42DC [DIN] (shown)
FCT / 4-20MA / 4-20MA / U [DIN]

Problem: We are using a common power supply for several loop powered transmitters that are wired back to different receiving devices and input cards. I am concerned about ground loop problems.

Cut Costs With Power Supply Sharing Problem Solvers Moore Industries
Download the PDF file

Solution: You should be! Use the ECT Signal Isolator/Converter. A single 24Vdc power supply can then power multiple loops. The ECTs break the galvanic path between devices and prevent the ground loops that can come from multiple devices sharing a common loop.

Model Number Example
ECT / 4-20MA / 4-20MA / 5.5VLP [DIN]

Problem: I have an odd-shaped storage tank. The output from my level transmitter doesn’t correspond to volume because of the nonlinear relationship. I have the strapping data for my tank, but my PLC is overloaded and can’t perform the linearization function. Any solutions?

Custom Linearization Handles Odd Shaped Tank Problem Solvers Moore Industries
Download the PDF file

 

Solution: The SIY PC-Programmable isolator has an 85-point linearization function that will easily handle this problem. Simply enter the strapping data into the table, and it will be linearized and scaled to provide a 4-20mA output proportional to volume.

Model Number Example
SIY / PRG / 4-20MA / 10-42DC [DIN]

Problem: We want to transmit the firing rate signal from our Boiler Control System (BCS) to our DCS for analysis. However, the BCS has a 0-10Vdc firing rate signal and the DCS will accept only 4-20mA.

Convert Signal for DCS Analysis Problem Solvers Moore Industries
Download the PDF file

Solution: Introduce the ECT Signal Converter to the loop. It accepts many non-standard inputs and delivers a 1000Vrms isolated 4-20mA output to your DCS.

Model Number Example
ECT / 0-10V / 4-20MA / 117AC [DIN]

Problem: We need a cost effective way to monitor and control our gas compressor engine using a PLC in an unmanned compressor station.

Compressor to PLC Interface Problem Solvers Moore Industries
Download the PDF file

Solution: Our FDY Frequency-toDC Transmitter accepts a frequency input from a mag pickup monitoring the gearing of a gas compressor engine. It converts this into a 4-20mA signal to send to the PLC so it can provide proportional engine control at a fraction of the cost of using frequency input cards for the PLC.

Model Number Example 
FDY / PRG / 4-20MA / 12-42DC [BH2NG]

Problem: How can I provide an additional HART output loop to share process signals between existing systems?

Additional HART Loops to Share Process Signals Problem Solvers Moore Industries
Download the PDF file

Solution: Use the HIT and HIX HART Isolators. They are single input/single output isolators that pass the digital component of the HART signal from the input to the output. The input can be connected inn series with the original HART loop before the isolated output is connected to an alternate receiver.

Model Number Example
HIX / 4-20mA / 4-20mA / 12-42DC [DIN]

Problem: We need to add a 250 ohm load (PID controller) to our temperature loop. However, this would exceed the 600 ohm loop maximum. Is there an inexpensive way to get around this problem?

 

Boost Power to an Overloaded Loop Problem Solvers Moore Industries
Download the PDF file

Solution: The low input impedance (25 ohms) and high drive capability (600 ohms) of our 2-wire ECT provides the increased capacity you need for your loop. You’ll have room for the new PID controller as well as future expandability.

Model Number Example
ECT / 4-20MA / 4-20MA / 12-42DC [DIN]

Problem: How can I implement a Safety Instrumented Function (SIF) into my Safety Instrumented System (SIS) and still monitor a critical signal or loop within an auxiliary system?

Using the SSX to Isolate Your Safety Instrumented System Problem Solvers Moore Industries 
Download the PDF file

Solution: The exida-approved, SIL 3-capable SSX Safety Signal Isolator provides area isolation between your SIS and auxiliary monitoring system. The SSX is output loop powered, so even if power is removed on the SSX’s output side, the SIS loop continues to function with no problems. Moreover, the SSX passes HART signals so critical diagnostic and calibration data can be seen on the output side of the SSX.

Model Number Example
SSX / 4-20mA / 4-20mA / 12-42DC [DIN]

Problem: How can I share a process signal that is part of my SIS (Safety Instrumented System) with my monitoring system that also uses a HART-based Asset Management package?

Passing HART Signals While Maintaining Safety Isolation Problem Solvers Moore Industries
Download the PDF file 

Solution: Use the 2-wire SSX Isolator. Its built-in HART pass-through technology allows for valuable HART data to be read on either side of the unit. Almost all other isolators block and “strip off” the HART signal. This allows you to isolate your Safety Instrumented System (SIS) from your process control or monitoring system and allows that valuable HART data to be passed on to your asset management package.

Model Number Example
SSX / 4-20mA / 4-20mA / 12-42DC [DIN]

Problem: Exothermic reactions in batch reactors can create thermal runaways where rising temperatures can lead to dangerous conditions.

Monitoring for Thermal Runaways Due to Exothermic Reactions Problem Solvers Moore Industries 
Download the PDF file

Solution: The SIL 2/3-capable STZ Functional Safety Dual Input Smart HART Temperature Transmitter allows either of the sensors or inputs to be designated as the primary measurement, with the secondary input acting as the backup sensor in case of primary sensor failure. This helps to mitigate potential thermal runaways before they become hazardous.

Model Number Example
STZ / PRG / 4-20MA / 12-42DC / [BH2NG]

 

Problem: Critical compressors often need an independent safety protection system to prevent over-speed conditions from developing which can damage equipment and endanger personnel and facilities.

Monitoring Critical Compressors to Prevent Over Speed Problem Solvers Moore Industries
Download the PDF file

Solution: The SFY can be used as part of the Safety Instrumented Function (SIF) to monitor compressor speed and provide data to a safety logic solver. To accomplish this, a magnetic pickup is attached to the compressor shaft. The pickup provides a frequency output. The SFY takes the pickup signal, converts it to a 4-20mA output proportional to the shaft speed, and transmits it to the SIS Logic Solver. Should there be an unwanted change in speed, it can be detected at the Logic Solver. This helps mitigate compressor damage or personnel injuries.

Model Number Example
SFY / PRG / 4-20MA / 12-42DC / [BH2NGP]

 

Page 1 of 6