Rugged instrumentation for reliable measurement and control

Applications By Industry

Search Applications

SPA2IS Controls and Monitors Wet Wells Wastewater Treatment Application

Wet WellProblem: Municipalities often have several wet well locations around a city that pump waste from low lying areas up to main sewage veins that feed waste treatment plants.  Level instruments monitor the wet well level and controllers then engage the grinder pumps.  Since wet wells contain waste, volatile gasses such as methane require that these level instruments be rated for use in Class I, Div 1 environments.

Solution: When IS (Intrinsic Safety) is chosen as the method of protection, a separate IS barrier is required for each level transmitter that is wired to the pump controller. The SPA2IS Alarm includes a built in IS barrier for the level instrument located in the wet well.  This means that the separate IS barrier does not have to be purchased, installed and maintained.  The SPA2IS has four alarms, each configurable with 0-100% deadband, which makes it an ideal fit for a wet well level controller.

SPA2IS Wet Well Diagram

Do you want more information? Download the data sheet. Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.

 

Download Datasheet