SPA2 Low Level Q:  Do you have a signal alarm unit for a tank level application? I need it to meet the following requirements:

  • Input signal accepts 4-20mA.
  • Contacts opened or relay de-energized @ EL 208 ft.
  • Equipped with up to four alarm trip relays.  
  • Individually configured for: set point, high or low trip, normally open or normally close, failsafe or non-failsafe, and latching or non-latching.
  • Deadbands adjustable over 100% of span.
  • Output relay equipped with form C contacts rated at 10A, 120VAC.
  • All operating parameters adjustable from the front panel keypad.
  • Operate on a 120V 60 Hz power source.
  • Capable of supplying 24V dc power to two-wire transmitters.

A: This is a perfect match for the Moore Industries SPA2 alarm trip unit.  The SPA2 can handle all of your above requirements, with an exception and a clarification.  Alarm set points for 208 feet should not be a problem assuming you have ranged your 4-20mA input to equal some engineering unit range of at least 208 feet, i.e. 4-20mA = 0-500 feet.  The exception is with the the form C relays on the SPA2.  They are rated for 5A, not 10A.  Therefore, if you need a 10A relay we recommend using an interposing relay in conjunction with the SPA2 outputs.  An example model number is: SPA2/HLPRG/4PRG/U [DIN]

Do you want more information? Download the data sheet. Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.

  • All
  • 330R2
  • Alarms
  • AlarmTrips
  • Application
  • Company
  • Demo
  • Fieldbus
  • FunctionalSafety
  • Functional Safety
  • HART
  • HCS Tutorials
  • I/PandP/I
  • Intrinsic Safety
  • ISOLATORS
  • LogicSolvers
  • Panels
  • RemoteI/O
  • SLA
  • SPA2
  • SPA2 Tutorials
  • SPA2IS Tutorials
  • STA Tutorials
  • TCS
  • Temperature
  • TemperatureSensors
  • TemperatureTransmitters
  • Tutorials
  • Default
  • Title
  • Date
  • Random
load more hold SHIFT key to load all load all