Telling the Difference Between a Low Signal and Lost Signal

ECA Alarm Trip no bkgQ: I have a question about the ECA-DIN Current and Voltage Alarm with the DH1L1 (Dual, High/Low, Failsafe) output option. The literature for the product says that "the failsafe relays are de-energized in an alarm condition or during power loss to the unit." Is this statement also true if there is a loss of input signal such as a broken wire?

A: The Failsafe setting means that the relay coils are de-energized in the alarm state. Naturally, if power is lost they will be de-energized. In case of loss of signal, the ECA will perceive the condition as a low signal and behave accordingly. That is, if you have a low alarm setting, the alarm will be activated. If you have a high alarm set, it will not be activated.
If you need more functionality such as being able to discern between a low signal and a lost signal, we recommend the SPA2. Unlike the ECA, it is a microprocessor-based design. This means that it can be configured for a variety of alarm and input signal conditions.

Do you want more information? Download the data sheet.  Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.

 

  • All
  • 330R2
  • Alarms
  • AlarmTrips
  • Application
  • Company
  • Demo
  • Fieldbus
  • Functional Safety
  • FunctionalSafety
  • HART
  • HCS Tutorials
  • I/PandP/I
  • Intrinsic Safety
  • ISOLATORS
  • LogicSolvers
  • Panels
  • RemoteI/O
  • SignalIsolation
  • SignalIsolators
  • SLA
  • SPA2
  • SPA2 Tutorials
  • SPA2IS Tutorials
  • STA Tutorials
  • TCS
  • Temperature
  • TemperatureSensors
  • TemperatureTransmitters
  • Tutorials
  • Default
  • Title
  • Date
  • Random
load more hold SHIFT key to load all load all