- Moore Industries Product Categories
- >
- Alarm Trips and Trip Amplifiers
- >
- NCS EMM -MAA
NCS NET Concentrator System with Multipoint Analog Alarm
Model: NCS EMM -MAA
The Multipoint Analog Alarm -MAA option for the Moore Industries NCS NET Concentrator System provides the ability to implement simple or dynamic alarming schemes without being a PLC programmer. A full NCS station with the -MAA option can have as many as 60 inputs, 32 alarms and eight physical relay outputs. Each of the 32 alarms can have a single input and a single relay output. Each of the eight relay outputs can be activated by a single alarm, multiple alarms or by all 32 alarms if desired. Minimum hardware configuration includes an EMM Ethernet MODBUS Module, ROM Remote Output Module, and any NCS Input module.
- PRODUCT DETAILS
- DATA SHEET
- MANUALS
- DRAWINGS
- SOFTWARE
- CERTIFICATION
Input Description | Programmable: Current, Voltage, RTD, T/C, mV, Ohms, Potentiometer, Discrete/Digital Contact |
Output Description | Eight Relay Outputs |
Power Description | 20-30DC |
Options Description | -MAA Multipoint Analog Alarm |
Housing Description | DIN-style housing mounts on 35mm Top Hat DIN-rails |
For use in Safety Instrumented Systems (SIS) | No |
Device Power | 24VDC |
Input | Universal: All Input Types, Discrete/Digital Contact |
Number of Alarm/Relay Outputs | 8 |
Analog Output | No |
Integral Display | No |
Intrinsically-Safe Input Connections | No |
Configuration/Setup | PC Configurable, Ethernet |
Housing/Enclosure | DIN Rail |
Hazardous Area Certifications | Non-Incendive/Div. 2, Zone 2 |
RoHS Compliant | Yes |
EMM Module (.dxf) | |
EMM Module (.dwg) | |
ROM Module (.dxf) | |
ROM Module (.dwg) | |
TIM Module (.dxf) | |
TIM Module (.dwg) | |
DIM Module (.dxf) | |
DIM Module (.dwg) | |
AIM Module (.dxf) | |
AIM Module (.dwg) |