Rugged instrumentation for reliable measurement and control

Applications By Industry


 

EHelp Tips: 535 Power up Using Remote Setpoint

535 ppQ. When the 535 1/4 DIN Single Loop PID Process Controller loses power with remote setpoint on, it comes back up in local setpoint mode. Is there a way to have the 535 always come back up in remote setpoint mode when power is restored?

A. Yes, the 535 can come back up with remote setpoint. To make the 535 power up using remote setpoint:

In the configurations menu

  1. Go to the SPECIALmenu 
  2. Go to PWR. UP: SP
  3. Select REMOTE

Details are on page 51 (number on the bottom right or page 58 of the PDF) in the user manual. For your convenience, the image is attached at the bottom of this page.

Check out more on the 535 1/4 DIN Single Loop PID Process Controller.  

Do you want more information? Download the data sheet. Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.