NCSQ. What product do you recommend that can take in a Modbus RTU serial signal and output multiple analog outputs? The serial signal can be from a fiber optic cable to remote devices or we can convert the signal from fiber optic to RS232 cable format.

A. Moore Industries’ NET Concentrator System Process Control and Distributed I/O (NCS) can be used for this. The NCS consists of a Modbus communications module (EMM) and a selection of I/O modules including a 4 channel analog output module (AOM). Multiple I/O modules can be plugged side-to-side and to the EMM to obtain the desired number of analog outputs. The EMM can function as a Modbus RTU Master, so it can query a number of Modbus RTU addresses on the RS485 data link. You will need a separate multimode or singlemode fiber to RS485 converter if you want to use fiber optic. 

Read more on the NCS.

Do you want more information? Download the data sheet. Or visit the catalog.

Need to get price or availability or have a technical question?

Send us a message using E-Help.