Q. I have an application that requires an analog splitter. The single input signal to the splitter comes from a transducer, and the transducer requires loop power. The two outputs are going to an analog monitoring card on a PLC, which provides power to the connected 4-20mA signal signals. Is the ECT what I need?
A. If you need a device with two outputs and with output loop power, the MIX would be a good choice. However, this model does not provide loop voltage to the input. It is a dual channel isolator so you would connect the input signal in series to the two input channels. MIX 2 and 4-channel models draw operating power from the loop output side, where power is typically made available by the receiving device, such as a DCS or PLC.
The ECT “Splitter” on the other hand provides loop voltage to the transducer, and it also provides the voltage to the two output loops. It requires a power source separate from the output signals.
You can specify either 24DC or 117AC for the separate power input. If the outputs must be compatible with a control system input card that is providing loop voltage then the EP option for the ECT modifies them to be passive. However, a separate power source is still required. The ECT offers Superior signal isolation (up to 1500Vrms). An ECT with the following model number would meet your application requirements: ECT/4-20MA/4-20MA/24VDC/-EP [DIN]
Quality and industrial strength protection stops ground loops, motor noise, and other electrical interference from affecting process signals. The ECT offers RFI/EMI protection against the unpredictable, harmful effects of radio frequency and electromagnetic interference. There is even a –RF option for enhanced protection in especially noisy environments.
Please visit our Interface Solution Download Center for more information on the MIX or the ECT line of products.
Do you want more information? Download the data sheet. Or visit the catalog.
Need to get price or availability or have a technical question?
Send us a message using E-Help.