Moore Industries: The Interface Solution Experts MooreHawke: Fieldbus Interface Solutions
Product Information
Signal Transmitters, Isolators and Converters
E-Help Express: Click Here First
Main Product Selection Index
Data Sheet Library
Installation Manual Library
CAD Drawing Library
Certifications & Safety-Related Instrumentation
Problem Solvers Application Notes
Add me to Email Technology Update List
Site Map
Chinese Web Site
Signal Transmitters, Isolators, and Converters Convert, isolate, split, boost, and step down process signals so field instruments can interface directly with indicators, recorders, DCS, PLC, and PC-based SCADA systems.

For more information, go to Problem Solvers Application Ideas and Capabilities.

New White Paper
NEW! Interactive White Paper
What can signal conditioners can do for you? Find out by reading this informative Interactive White Paper Signal Isolators, Converters and Interfaces: The "Ins" and "Outs" ( 1.1M )


 

Detailed product data sheets are available in PDF format by clicking on the product names below. PDF files require Adobe Reader, which can be downloaded free from Adobe's Web site.

USB Cable Now Available for PC-Programmable Interface Instruments!
In addition to our FREE serial Configuration Cable, we now offer (for a nominal charge) a USB Communication Cable for Moore Industries' PC-Programmable Instruments. Get Data Sheet (477K)

Featured Interface Solutions
Model Input Output Power Mounting
MIX & MIT miniMOORE™ 2-Wire and 4-Wire Multi-Channel Signal Isolators and Converters

MIX & MIT

Get Data Sheet
mix_mit.pdf ( 616K )

Switch Selectable on 2-Channel Models
4-20mA
0-5V
1-5V
0-10V

Fixed 4-20mA input/4-20mA Output on 4-Channel MIX Models

Two (MIX & MIT) 4-20mA or Four (MIX) 4-20mA Channels Model MIX: 2-Wire,
Output Loop-Powered
(12-42DC)

Model MIT: 4-Wire,
Line/Mains-Powered
(Universal for any range between 20-375Vdc or 90-264Vac)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
ECT-DIN 2- and 4-Wire Signal Isolators, Converters, Repeaters, and Splitters

ECT-DIN

Get Data Sheet
ect_din.pdf (166K )

4-20mA
1-5Vdc
0-150Vac
0-5Aac
4-20mA
Dual Output Channels for Signal Splitting
2-Wire,
Output Loop-Powered
(10-42Vdc)

2-Wire,
Input Loop-Powered
(5.5 volts loop-powered)

4-Wire,
Line-Powered
(24Vdc, 117Vac, or 230Vac)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
SIY 2-Wire PC-Programmable Signal Isolator and Converter

SIY

Get Data Sheet
siy.pdf (397K )

Sets Up in One Minute, From One Software Window
Current
Any range from
-2.5 to 55mA including:
0-20mA
4-20mA
10-50mA
Voltage
Any range from
-0.5 to 11V including:
1-5Vdc
0-10Vdc
4-20mA 2-Wire,
Output Loop-Powered
(10-42Vdc)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Field Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)
SIX 2-Wire Signal Isolator, Converter, and Repeater

SIX

Get Data Sheet
six.pdf (130K )

0-20mA
4-20mA
10-50mA
0-1mA
-1 to +1mA
-10 to +1-Vdc
0.2-1Vdc
0-1Vdc
0-5Vdc
1-5Vdc
0-10Vdc
0-30Vdc
4-20mA
10-50mA
2-Wire,
Output Loop-Powered
(12-42Vdc)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
CPT 4-Wire PC-Programmable Signal Isolator and Converter

CPT

Get Data Sheet
cpt.pdf (356K )

Sets Up in One Minute, From One Software Window
Current
Any range from 0 to 50mA including:
0-20mA
4-20mA
10-50mA
Voltage
Any range from 0 to 10Vdc including:
1-5Vdc
0-10Vdc

Sensor (RTD and T/C) inputs are also available. See the data sheet for details.
Sets Up in One Minute, From One Software Window
Current
Any range from 0 to 20mA including:
0-20mA
4-20mA
Voltage
Any range from 0 to 10Vdc including:
1-5Vdc
0-10Vdc
Optional Relay Output Warns of Unwanted Process Conditions
High/Low Alarms
(Failsafe or Non-Failsafe)
4-Wire,
Line-Powered
(24Vdc, 117Vac, or 230Vac)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
TMZ 4-Wire PC-Programmable MODBUS Signal Transmitter

TMZ

Get Data Sheet
TMZ.pdf (308K )

Sets Up in One Minute, From One Software Window
Current
Any range from 0 to 50mA including:
0-20mA
4-20mA
10-50mA
Voltage
Any range from 0 to 10Vdc including:
1-5Vdc
0-10Vdc

Sensor (RTD and T/C) inputs are also available. See the data sheet for details.
MODBUS RTU
(RS-485)
Communications

4-Wire,
Line-Powered
(24Vdc)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
FCT 4-Wire Field-Configurable Signal Isolator and Converter

FCT

Get Data Sheet
fct.pdf ( 81K )

Field Configurable
0-20mA
4-20mA
0-50mA
10-50mA
0-5Vdc
1-5Vdc
0-10Vdc
Special Ranges
Field Configurable with Jumpers
0-20mA
4-20mA
0-5Vdc
1-5Vdc
0-10Vdc
Special Ranges
Takes any Power Supply
4-Wire, Universal Line-Powered
(accepts 22-300Vdc or 90-260Vac)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)
HIT and HIX 2- and 4-Wire HART® Isolators

HIT, HIX

Get Data Sheet
hit_hix.pdf (571K )

4-20mA
input with superimposed HART digital protocol signal
Isolates Loop, Lets HART Digital Signal "Pass Through"
4-20mA
output with superimposed HART digital protocol signal
HIT
4-wire line-powered
(24Vdc, 117Vac, 230Vac)

HIX
2-wire loop-powered
(12-42DC)
Thermoplastic DIN-style
(G-type and Top Hat rails)
SCX 2-Wire Signal Isolator and Converter

SCX

Get Data Sheet
scx.pdf (159K )

4-20mA
10-50mA
4-20mA
10-50mA
Special Ranges
2-Wire,
Input Loop-Powered
(5.5, 4.5, or 8.5 volts loop powered)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Field-Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)
ACX 2-Wire AC Current Isolator and Transmitter

ACX

Get Data Sheet
acx.pdf (123K )

0-1Aac
0-2Aac
0-3Aac
0-4Aac
0-5Aac
0-0.5Vac
0-1.5Vac
0-5Vac
0-10Vac
0-25Vac
0-50Vac
0-120Vac
0-150Vac
4-20mA
10-50mA
2-Wire,
Output Loop-Powered
(10-42Vdc)
High-Density and RFI Resistant
Aluminum DIN-style
(G-type and Top Hat rails)

Field-Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)
SDY 2-Wire PC-Programmable Signal Isolator and Converter with Display

SDY

Get Data Sheet
sdy.pdf (296K )

Sets Up in One Minute, From One Software Window
Current
Any range from
-2.5 to 55mA including:
0-20mA
4-20mA
10-50mA
Voltage
Any range from
-0.5 to 11V including:
1-5Vdc
0-10Vdc
Easy-to-Read Display
4-20mA
2-Wire,
Output Loop-Powered
(10-42Vdc)
Field Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)
FDY 2-Wire PC-Programmable Frequency-to-DC Transmitter with Display

FDY

Get Data Sheet
fdy.pdf (277K )

Sets Up in One Minute, From One Software Window

Frequency
0.005Hz to 25KHz Ranges

Periods
40 microseconds to 200 seconds

Pulse Widths
0.2 milliseconds to 200 seconds
User-Configurable Display Shows Any Engineering Unit
4-20mA
2-Wire, Output Loop-Powered (12-42DC) Field-Mount
Hockey-Puck
(head, pipe, relay-track, surface, and explosion-proof)