A customer has a Safety Instrumented Function they need to implement with two independent level transmitters (radar), each wired to a separate STA Functional Safety Trip Alarm. The process will trip if either level reaches the set point, for example a 1 out of 2 (1oo2) voting. However, if the alarm trip (STA) detects an input or unit fault. The customer did not want the process to trip. Instead they wanted to take the faulty unit out of service leaving the process running with the one good level and alarm trip. 
Published: November 28, 2017

Detailed Description of Converting Dry Contacts to Analog Signals

Before converting a dry contact to an analog signal it is important to first determine what signal levels you will need.  Since the TMZ accepts a 4-20mA signal then we can choose any current values within 4mA and 20mA.  For this application we chose 'NOT FULL' to be equal to 20mA, and “NEAR FULL” to be represented at 4mA. 